Plan Review Notes
Plan Review Notes For Permit 09120427
Permit Number 09120427
Review Stop M
Sequence Number 1
Notes
Date Text
2010-01-11 18:08:34REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-3 SHOWS DUCT SMOKE DETECTOR INSTALLED ON THE
 RETURN DUCT WHILE PACKAGE UNIT SCHEDULE CALLS FOR
 DETECTOR IN THE SUPPLY. SMOKE DETECTOR SHALL BE
 INSTALLED ON THE SUPPLY DUCT IN ACCORDANCE WITH FBC-M
 606.2.1. COORDINATE FLOOR PLAN AND SCHEDULE TO SHOW THE
 CORRECT LOCATION (SUPPLY).
  
 2. ENGINEERING BUSINESS LICENSE NUMBER (CERTIFICATE OF
 AUTHORIZATION) SHALL APPEAR IN THE TITLE BLOCK IN
 ACCORDANCE WITH FFAC RULE 61G15-23.002. SIMILAR
 REQUIREMENTS EXIST FOR THE ARCHITECTURAL BUSINESS.
  
 3. PLAN SHOWS PACKAGE UNIT AND DUCTWORK LOCATED
 OUTDOORS. NO INFORMATION WAS PROVIDED REGARDING OUTDOOR
 INSTALLATIONS AND WIND RESISTANCE. OUTDOOR APPLIANCES
 AND DUCTWORK SHALL BE DEIGNED AND INSTALLED FOR WIND
 RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. PROVIDE
 MANUFACTURER'S DATA FOR THE WIND RESISTANCE CABILITIES
 OF THE PACKAGE UNIT WITH ENGINEERED INSTALLATION
 DETATIL FOR THE PACKAGE UNIT AND OUTDOOR DUCTWORK.
  
 4. PAGE M-1 MECHANICAL NOTE #7 CALLS FOR CONDENSATE TO
 BE DISCHARGED TO THE NEAREST DRAIN. CONDENSATE SHALL
 NOT DISCHARGE TO THE SANITARY SEWER SYSTEM PER CITY
 ORDINANCE. CONDENSATE SHALL DISCHARGE TO AN APPROVED
 LOCATION (SUCH AS A PERVIOUS AREA AT LEAST 12" FROM THE
 BUILDING) IN ACCORDANCE WITH FBC-M 307.2.1.
  
 5. MECHANICAL NOTES AND OUTSIDE AIR SCHEDULE REFERENCE
 THE INTERNATIONAL CODES AND GEORGIA AMENDMENTS. PLEASE
 CORRECT ALL CODE REFERENCES TO THE 2007 FLORIDA
 BUILDING CODE WITH 2009 SUPPLEMENTS, WHICH IS THE CODE
 IN EFFECT IN FLORIDA AS OF MARCH 1, 2009.
  
 6. FAN SCHEDULE NOTE #4 CALLS FOR "INLINE" EF-2 TO BE
 MOUNTED ON A ROOF CURB WHILE FLOOR PLAN SHOWS THE FAN
 INSIDE THE BUILDING. PLEASE CLARIFY. AN OUTDOOR FAN
 WILL BE SUBJECT TO THE WIND RESISTANCE REQUIREMENTS AS
 STATED IN COMMENT #3 ABOVE.
  
 7. PACKAGE UNIT SCEDULE, VAV SCHEDULE AND FLOOR PLANS
 DO NOT CORRESPOND. SEE EXAMPLES.
  
 EXAMPLE: TOTAL MAX CFM FOR ALL VAV SYSTEMS IS
 SIGNIFICANTLY LESS THAN THE 6000 BEING PROVIDED BY THE
 PACKAGE SYSTEM.
 EXAMPLE: VAV SCHEDULE GIVES A MAX CFM OF 900 FOR VAV-1
 WHILE THE FLOOR PLAN CALLS FOR 1900 CFM.
  
 THESE ARE EXAMPLES OF DISCREPANCIES AND NOT AN
 EXHAUSTIVE LIST. COORDINATE VOLUMES AND SIZES OF ALL
 EQUIPMENT AND AIR DISTRIBUTION COMPONENTS TO SHOW THE
 REQUIRED AIRFLOWS IN ACCORDANCE WITH FBC-M 603.1.
  
 8. OUTSIDE AIR INTAKE ON THE PACKAGE UNIT SHALL BE
 EQUIPPED WITH A MOTORIZED VOLUME DAMPER WITH SHUTOFF
 DAMPER CONTROLS IN ACCORDANCE WITH FBC-B 13-407.AB.3.3.
  
 9. ISOLATION ROOM 111 DOES NOT SHOW ANY MEANS FOR
 RETURN AIR. BALANCED RETURN AIR WITH MINIMAL PRESSURE
 DIFFERENTIALS IS REQUIRED. SHOW HOW BALANCED RETURN IS
 TO BE ACHIEVED IN THIS ROOM IN ACCORDANCE WITH FBC-M
 601.4.
  