| Plan Review Notes For Permit 09120427 |
| Permit Number |
09120427 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-30 16:14:21 | *****DENIED***** INCOMPLETE | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | WHICH IS BASED ON NFPA 101, LIFE SAFETY CODE, 2006 | | | EDITION AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION | | | SHALL BE REFERENCED. THIS OCCUPANCY SHALL BE CLASSIFIED | | | AS EXISTING HEALTH CARE (CHAPTER 19 OF NFPA 101). | | | | | | 3. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE | | | TO THE EXITS, LOCATION OF FIRE EXTINGUISHER(S), AND ANY | | | OTHER DETAILS PERTINENT WITH THE LIFE SAFETY FEATURES | | | OF THIS PROJECT LOCATION. | | | | | | 4. SPECIFY THE INTERIOR FINISH MATERIALS IN TERMS OF | | | CLASS A OR CLASS B. | | | | | | 5. PROVIDE A LAYOUT OF THE FIRE SPRINKLERS HEADS FOR | | | THE PROJECT SITE LOCATION. HOW WILL THE REMODEL HAVE AN | | | AFFECT UPON THIS SYSTEM? | | | | | | 6. ON THE FLOOR PLAN, SHEET A-1A, PLEASE EXPLAIN WHY | | | THE DOOR IN ROOM 27 IS BLOCKED BY THE STOCKING OF THE | | | WHEEL CHAIRS. | | | | | | 7. PROVIDE THE PRESCRIPTIVE STRENGHTS FOR THE | | | GUARDRAILS AND HANDRAILS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | |
|