Plan Review Notes
Plan Review Notes For Permit 09120427
Permit Number 09120427
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-29 10:39:35 
 ** DENIED REVIEW **
  
 **09120427
  
  
 1) NOTE: PLANS SUBMITTED UNDER TBD FOR CONTRACTOR. ONCE
 PLANS ARE FOUND CODE COMPLIANT AS WELL AS MEETING ALL
 ADOPTED STATUTORY REQUIREMENTS THE REVIEW WILL STILL BE
 IN FAILED STATUS UNTIL PROPERLY LICENSED CONTRACTOR HAS
 APPLIED FOR PERMIT.
 ** IMPORTANT
 THE APPLIED VALUE FOR THE COMPLETE SCOPE OF WORK IS
 VERY LOW. THE VALUE SHALL INCLUDE ALL DESIGN COSTS,
 LABOR, EQUIPMENT AND MATERIALS EVEN IF ANY OF THESE
 ITEMS ARE OWNER SUPPLIED.
 FBC 108.3 AS ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 2) NOTE: ARCHITECTURAL PLANS ARE NOT DATED AND SEALED
 AS REQUIRED. PLEASE SEE FLORIDA STATUTES 481.221 WHICH
 REQUIRES ARCHITECT TO DATE PLANS WHEN SIGNING AND
 SEALING.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G1-16.002
 WHICH REQUIRES SEAL TO BE AN *IMPRESSION TYPE SEAL*.
 THE USE OF A RUBBER STAMP IN LIEU OF THE IMPRESSION
 TYPE SEAL IS NOT PERMITTED.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 3) NOTE: ARCHITECTURAL TITLE BLOCK REQUIRES THE FIRM
 LICENSE NUMBER ALSO KNOW AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER TO BE LISTED ON TITLE BLOCKS.
 PLEASE SEE FAC61G1-16.04 WHICH REQUIRES THE NUMBER TO
 BE ON TITLE BLOCKS.
 PLEASE SEE FS 481.219 WHICH REQUIRES FIRM TO HAVE A
 CERTIFICATE OF AUTHORIZATION NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 4) NOTE: ENGINEERING FIRM IS REQUIRED TO HAVE THE FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER LISTED ON THE TITLE BLOCKS.
 PLEASE SEE FAC 61G15-23.002 WHICH REQUIRES INFORMATION
 ON TITLE BLOCKS.
 PLEASE SEE FS 471.025 WHICH REQUIRES THE C OF A NUMBER.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 ANY OTHER TRADE.
  
 5) NOTE: PLANS CONTAIN CODE REFERENCES WHICH NEED TO BE
 ADJUSTED. SEE SOME ITEMS FOR EXAMPLE: M-SHEETS WHICH
 LIST THE 2006 INTERNATIONAL MECHANICAL CODE WITH 2007
 GEORGIA AMENDMENTS. THE SCOPE OF WORK IS BEING DONE IN
 THE STATE OF FLORIDA. PLEASE ADJUST.
  
 THE PLANS LIST THE 2007 FBC FOR ELECTRICAL CODE HOWEVER
 BASED ON WHEN PERMIT APPLICATION IS MADE THIS WILL
 GOVERN WHICH NFPA-70 THE DESIGN IS REQUIRED TO MEET.
 THIS PERMIT APPLICATION WAS MADE AFTER OCTOBER 1ST
 ,2009. THIS PLACES THE PROJECT UNDER THE SECOND SET OF
 2009 SUPPLEMENTS ADOPTED UNDER THE 2007 FBC. AS OF
 10/1/09 THE ELECTRICAL IS REQUIRED TO BE 2008 NFPA-70 (
 NEC).
 ** PLEASE SEE 2008 NEC FOR SUBSTANTIAL CHANGES.
  
 THE NFPA-101A LISTED ON PLANS STATE 2004. THE STATE OF
 FLORIDA FIRE MARSHAL AND FLORIDA BUILDING CODE DOES NOT
 ADOPTED NFPA-101A.
 PLEASE SEE FAC 69A-60.004 WHICH ADOPTED THE 2006
 NFPA-101.
 PLEASE SEE FAC 69A-60.003 WHICH ADOPTED THE 2006
 NFPA-1.
  
  
 ** IT IS IMPORTANT TO KNOW THAT THERE WERE TWO
 SUBSTANTIAL REVISIONS TO THE 2007 FBC FOR ENERGY CODE
 REQUIREMENTS UNDER CHAPTER 13.
  
 6) NOTE: NO AUTOMATED LIGHTING CONTROLS SHOWN ON PLANS
 AS REQUIRED PER FBC 13-415.AB.1.1,.1.2 AND .1.3.
 NOT ALL AREAS ARE EXEMPT.
  
 7) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS WERE
 SUBMITTED. PLEASE SEE FBC 13-415.AB.5 FOR REQUIRED
 INTERIOR LIGHTING PERFORMANCE CALCULATIONS.
 MUST MEET MINIMUM PRESCRIPTIVE.
  
 8) NOTE: FIRE ALARM SYSTEM IS REQUIRED TO BE UNDER
 SEPARATE PERMITS HOWEVER BASE PLANS ARE REQUIRED
 MINIMUM DESIGN INTENT. PLEASE SEE FBC 11-4.28.1,.2 AND
 .3(4) FOR MINIMUM LOCATIONS, HEIGHTS AND LEVELS OF
 HORNS AND STROBE FOR ADA COMPLIANCE. THE STATE OF
 FLORIDA CHAPTER 11 FOR ACCESSIBILITY IS MORE STRINGENT
 THAN NFPA-72 AS NOTED ON FIRE ALARM NOTES.
  
 9) NOTE: THERE IS A NOTE #14 ON SHEET E-2 WHICH
 MENTIONS A MANUAL TRANSFER SWITCH HOWEVER NO
 INFORMATION SUCH AS PRODUCT SPECIFICATIONS ARE
 SUBMITTED. PLEASE SUBMIT MANUFACTURE SPECS/CUT SHEETS.
 PLEASE PROVIDE INFORMATION ON ANY OF THE SYSTEMS
 BESIDES THE BATTERY BACKED UP EMERGENCY LIGHTS WILL
 ALSO REQUIRE BACK UP POWER. LEGALLY REQUIRED OR LIFE
 SAFETY SYSTEM SHALL BE BACKED UP BY ONE OF THE
 ACCEPTABLE BACK UP POWER STANDARDS.
 PLANS CONTAIN NOTES AND CODES WHICH INDICATE THAT PLANS
 SHOULD HAVE BEEN SUBMITTED AND REVIEWED BY ACHA. PLEASE
 SUBMIT THE DOCUMENTATION/LETTER FROM THEIR REVIEW OF
 THE SUBMITTED PLANS.
  
  
 NFPA-99, NFPA-70; 700,701, 110.3, 90.7, 517 PART III
 ETC
  
 10) NOTE: PLEASE INDICATE REDUNDANT GROUNDING PER
 517.13.
  
 11) NOTE: PLANS DO INDICATE SOME SORT OF DOOR CONTROLS
 SUCH AS ACCESS CONTROL SYSTEM HOWEVER NO SPECIFIC
 DETAILS IS PROVIDED. ACCESS CONTROL SYSTEMS ARE
 REQUIRED TO BE UNDER SEPARATE LOW VOLTAGE PERMITS.
 NFPA-101 CHAPTER 7 IS APPLICABLE WHEN SUBMITTING PLANS
 AND PERMIT APPLICATION FOR THE SCOPE OF WORK.
 PLEASE SEE 7.2 AND CALL ELECTRICAL REVIEW AND FIRE
 MARSHAL FOR QUESTIONS.
  
 12) NOTE: ALL EXTERIOR LIGHTING CONTROLS SHALL MEET FBC
 13-415.AB.1.4. THE PHOTO-CELL CONTROL SHOWN MUST BE
 CONNECTED TO BE THE OVER RIDE NOT THE TIME CLOCK. IF
 USING A TIME CLOCK AS THE OVER RIDE THEN IT MUST BE
 ASTRONOMICAL WITH A MINIMUM OF 10HR PROGRAMMING BACK
 UP.
  
 13) NOTE: WHEEL CHAIR STORAGE IS NOT PERMITTED IN FRONT
 OF ELECTRICAL ROOM DOOR. 240.24,110.26
  
 14) NOTE: PLEASE SEE 422.13 WHICH WERE REVISED UNDER
 THE 2005 NEC. ELECTRIC STORAGE TYPE WATER HEATERS ARE
 CONSIDERED CONTINUOUS LOADS.
 SEE CODE COMMENTARY IN HANDBOOK.
  
 15) NOTE: RISER INDICATES ADDING A NEW BREAKER TO THE
 EXISTING MAIN FEEDING NEW SERVICE EQUIPMENT HOWEVER NO
 LOAD CALCULATIONS WERE SUBMITTED FOR THE EXISTING
 SERVICE ADDING NEW.
 PLEASE SUBMIT LOAD ON EXISTING MAIN WITH NEW LOADS
 BEING ADDED.
 NEC 220
  
  
 IF THERE IS NO WORK FOR ELECTRICAL THEN PERMIT APPLIED
 IS TO BE VOIDED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  