| 2009-12-28 08:43:17 | 2007 FBC W/2009 REVISIONS |
| | LEVEL 2 ALTERATION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) INDICATE THE SUITE OR UNIT NUMBER ON THE PLANS AND |
| | APPLICATION. |
| | |
| | 2) SPECIFY THE LEVEL OF ALTERATION PER 2007 FBC |
| | EXISTING BUILDING ON THE PLANS. |
| | |
| | 3) SPECIFY THE TYPE OF CONSTRUCTION BASED ON THE 2007 |
| | FBC DESIGNATIONS AS LISTED IN TABLE 602. TYPE IV |
| | CONSTRUCTION WHICH IS STATED ON THE PLANS IS HEAVY |
| | TIMBER CONSTRUCTION IN THIS TABLE. PLEASE CORRECT. |
| | |
| | 4) PLEASE SEE TABLE 601 IN THE 2007 FBC FOR THE |
| | REQUIRED FIRE RESISTANCE RATINGS FOR BUILDING ELEMENTS. |
| | ALSO PLEASE NOTE THAT THE CODE NO LONGER USES THE ONE |
| | HOUR PROTECTED DESIGNATION. INSTEAD USING THE LETTERS A |
| | OR B AFTER THE CONSTRUCTION TYPE, WITH THE A BEING |
| | SIMILAR TO ONE HOUR PROTECTED. |
| | |
| | 5) PROVIDE A LIFE SAFETY PLAN FOR THE ALTERED AREA. |
| | SPECIFY TRAVEL DISTANCES, COMMON PATHS OF TRAVEL, SHOW |
| | EXIT SIGNS, FIRE EXTINGUISHER LOCATIONS, ETC. |
| | |
| | 6) SUBMIT A FIRE SPRINKLER PLAN. |
| | |
| | 7) SPECIFY THE AMOUNT AND TYPES OF HAZARDOUS |
| | MATERIALS/CHEMICALS THAT WILL BE STORED AND USED IN THE |
| | BICARB AND WATER TREATMENT ROOMS. SUBMIT MATERIAL |
| | SAFETY DATA SHEETS FOR ALL HAZARDOUS MATERIALS. SHOW |
| | COMPLIANCE WITH 2007 FBC SECTIONS 307, 414 AND 415 AS |
| | APPLICABLE. |
| | |
| | 8) INDICATE THE USE FOR THE ROOM WHICH HAS DOOR 27 THAT |
| | IS BEING BLOCKED BY WHEEL CHAIR STORAGE. CLARIFY WHY IS |
| | THIS DOOR IS BEING BLOCKED. |
| | |
| | 9) SUBMIT PRODUCT APPROVALS FOR THE NEW EXTERIOR DOORS |
| | AS REQUIRED BY DCA RULE 9B-72. THE DESIGNER OF RECORD |
| | IS REQUIRED TO REVIEW AND APPROVE THE PRODUCT APPROVALS |
| | IN WRITING. |
| | |
| | 10) SPECIFY THE REQUIRED COMPONENT AND CLADDING WIND |
| | LOAD PRESSURES ON THE PLANS FOR THE NEW EXTERIOR DOORS. |
| | FBC 1604.9 |
| | |
| | 11) SPECIFY THE WIND DESIGN DATA ON THE PLANS. FBC |
| | 1603.1.4 |
| | |
| | 12) SHOW THAT THE NEW EXTERIOR DOORS WILL MEET IMPACT |
| | REQUIREMENTS OF FBC 1609.1.2. |
| | |
| | 13) PROVIDE STRUCTURAL DETAILS FOR THE NEW EXTERIOR |
| | DOOR OPENINGS ON THE PLANS. FBC 1609.1 |
| | |
| | 14) PROVIDE DOOR BUCK ANCHORING DETAILS. FBC 1714.5.4.2 |
| | |
| | 15) THE DOOR SCHEDULE ON SHEET A-4 IS INCOMPLETE. |
| | PLEASE LIST ALL DOORS THAT ARE TAGGED INCLUDING THE |
| | EXISTING ONES. |
| | |
| | 16) THE INFORMATION FOR DOOR 112 TO THE TOILET ROOM IS |
| | NOT LISTED AND DOOR 113 IS TO THE JANITOR CLOSET. |
| | |
| | 17) PROVIDE A DETAIL OF THE ONE HOUR FIRE RATED WALL UL |
| | X536 ON THE PLANS. |
| | |
| | 18) THE HANDRAIL DETAILS FOR THE STAIRS ON SHEET A-3C |
| | DO NOT COMPLY WITH FBC 11-4.9.4 (2). |
| | |
| | 19) PROVIDE DETAILS OF EXTERIOR STAIRS SHOWING |
| | COMPLIANCE WITH FBC 11-4.9. |
| | |
| | 20) FBC 11-4.8.5(2) REQUIRES HANDRAILS ON RAMPS THAT |
| | ARE NOT CONTINUOUS TO EXTEND 18" BEYOND THE SLOPE |
| | SEGMENT AND BE PARALLEL TO THE FLOOR OR GROUND SURFACE. |
| | (FLORIDA SPECIFIC) |
| | |
| | 21) PROVIDE A DETAIL FOR THE RAMP SHOWING ALL |
| | DIMENSIONS. SHOW COMPLIANCE WITH FBC 11-4.8.3 (FL |
| | SPECIFIC EXCEPTION) THAT REQUIRES RAMPS THAT ARE PART |
| | OF A MEANS OF EGRESS TO BE A MINIMUM OF 44" WIDE. |
| | |
| | 22) SHOW COMPLIANCE WITH FBC 11-4.8.4 (2) (FL SPECIFIC) |
| | WHICH REQUIRES LANDINGS ON RAMPS TO BE NOT LESS THAN 60 |
| | INCHES CLEAR AND THE BOTTOM OF THE RAMP TO HAVE NOT |
| | LESS THAN 72 INCHES OF STRAIGHT AND LEVEL CLEARANCE. |
| | |
| | 23) SHOW COMPLIANCE WITH FBC 11-4.8.5 (1) HANDRAILS AT |
| | RAMP SEGMENTS ARE REQUIRED TO BE CONTINUOUS AND FBC |
| | 11-4.8.7 REQUIRING EDGE PROTECTION FOR RAMPS AND |
| | LANDINGS WITH DROP OFFS. |
| | |
| | 24) SHOW COMPLIANCE WITH FBC 11-4.8..6 WHICH REQUIRES |
| | THE CROSS SLOPE OF RAMP SURFACES TO BE NO MORE THAN |
| | 1:50. CHECK THE ELEVATIONS ON C1 FOR CROSS SLOPES. |
| | |
| | 25) THE PLANS ARE REQUIRED TO BE SEALED WITH THE |
| | ARCHITECT'S IMPRESSION TYPE SEAL PER FAC 61G1- 16.001. |
| | |
| | 26) THE LICENSE NUMBER OF THE ARCHITECTURAL FIRM IS |
| | REQUIRED TO BE IN THE TITLE BLOCK PER 61G1-16.004. |
| | |
| | 27) PLEASE RESPOND TO REVIEW COMMENTS IN WRITING |
| | INDICATING HOW THE COMMENTS WERE ADDRESSED AND THE |
| | LOCATION OF THE CORRECTIONS ON THE PLANS. |
| | |