| 2010-01-04 12:02:12 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. SHOW COMPLIANCE WITH FBC TABLE 503 AND FBC TABLE |
| | 602. A SITE PLAN SHOULD BE PROVIDED WHICH SHOWS |
| | DISTANCE BETWEEN BUILDINGS, DISTANCE FROM PROPOSED NEW |
| | BUILDING TO THE PROPERTY LINE, BUILDING TYPE (FBC CH 6) |
| | AND OCCUPANCY CLASSIFICATION (FBC CH 3). MORE |
| | INFORMATION MAY BE REQUIRED. ENOUGH INFORMATION SHOULD |
| | BE PROVIDED TO SHOW COMPLIANCE WITH FBC TABLE 503 AND |
| | FBC TABLE 602. |
| | |
| | 2. PROVIDE INFORMATION REGARDING THE PROPOSED NEW |
| | RELOCATED BUILDING. FOR THE BUILDING TO BE RELOCATED, |
| | PROVIDE EITHER A COPY OF THE ORIGINAL PERMIT PLANS, A |
| | COPY OF THE DCA APPROVED PLAN, OR A SIGNED AND SEALED |
| | SET OF AS-BUILT PLANS. YOU MAY FIND THE DCA WEBSITE |
| | HELPFUL: |
| | |
| | HTTP://WWW.DCA.STATE.FL.US/FBC/MANUFACTURED_BUILDINGS/Q |
| | &A-0108_V3.PDF |
| | |
| | 3. DECLARE OCCUPANCY CLASSIFICATION FOR THIS STRUCTURE |
| | AND EITHER REVISE THE PLANS TO SHOW COMPLIANCE WITH FBC |
| | CHAPTER 11 OR INCORPORATE EXCEPTION INTO THE PLAN. SEE |
| | OTHER COMMENTS. |
| | |
| | 4. THE PLAN SHOWS THE STRUCTURE AT 1'4" ABOVE GRADE. |
| | DOES THE STRUCTURE INCLUDE STAIRS FOR ACCESS AS A PART |
| | OF THE DCA APPROVAL, OR IS THIS TO BE SITE BUILT? SEE |
| | FBC CHAPTER 10. PROVIDE DETAILS AS REQUIRED. |
| | |
| | 5. NOT ENOUGH INFORMATION WAS PROVIDED TO DETERMINE |
| | CODE COMPLIANCE. THE PLANS STATE THAT AN "EXISTING |
| | WOODY WASTE TRAILER" IS TO BE REPLACED, BUT BASED ON |
| | THE FLOOR PLAN IT APPEARS THAT THE NEW TRAILER CONTAINS |
| | OFFICES OR WORK AREAS. |
| | |