| 2009-12-30 10:57:59 | |
| | ** DENIED /PROVISO ** |
| | |
| | **REVISION REQUIRED |
| | |
| | |
| | |
| | |
| | 1) NOTE: THE SUBMITTED FLACOM ENERGY CALCULATIONS ARE |
| | NOT CODE COMPLIANT. THERE WERE 4 COPIES SUBMITTED. TWO |
| | COPIES ATTACHED TO PLANS AND TWO COPIES IN PACKAGE. ONE |
| | SIGNED AND SEALED IN SEPTEMBER AND THE OTHER IN |
| | DECEMBER. IN EITHER CASE COMMENTS REMAIN THE SAME FOR |
| | ALL SUBMITTED. |
| | THE INPUT DATA REPORT NEEDS TO COORDINATE WITH THE |
| | PLANS FOR ALL BUILDING COMPONENTS. SEE COMMENTS FROM |
| | OTHER TRADES FOR OTHER SYSTEMS OTHER THAN ELECTRICAL. |
| | NOT ALL SYSTEMS FOR OTHER TRADES ARE WHAT IS SHOWN ON |
| | PLANS. |
| | 13-415.2, 13-415.2.ABC.1.1, 13-415.ABC.1.2 |
| | |
| | A) THE IDR INDICATES ON EXTERIOR LIGHTING PORTION |
| | LIGHTING WHICH IS DESIGNATED FOR HISTORIC. THERE IS NO |
| | HISTORIC LANDMARK DESIGNATION ON THIS PROJECT. |
| | THE IDR INDICATES ON THE EXTERIOR LIGHTING PORTION |
| | LIGHTING WHICH IS DESIGNATED BY *HEALTH, SAFETY, |
| | STATUTE ETC*. THERE ARE NO STATUTES, LAWS OR OTHER |
| | CODES WHICH REQUIRE THE LIGHTING ON THE EXTERIOR OF |
| | THIS BUILDING. |
| | BY ENTERING THE ABOVE AS SUCH ON THE IDR, IT WILL |
| | EXEMPT THE LIGHTING FROM THE CALCULATIONS. THERE IS NO |
| | EXEMPT EXTERIOR LIGHTING. |
| | ** PLEASE ADJUST THE ABOVE FOR EXTERIOR LIGHTING. |
| | |
| | B) THE IDR INDICATES ALL INTERIOR LIGHTING CONTROLS AS |
| | *MANUAL ON/OFF* WHICH IS NOT THE CASE. |
| | C) THE IDR INDICATES ALL INTERIOR LIGHTING AS * COMPACT |
| | FLORESCENT* FOR ALL LIGHTING. THIS IS NOT WHAT IS ON |
| | THE PLANS. |
| | D) THE PLANS INDICATE NUMEROUS S5 FIXTURES HOWEVER |
| | THERE ARE NO S5 FIXTURES ON THE IDR. |
| | E) THE PLANS INDICATE *D* FIXTURES HOWEVER THERE ARE NO |
| | *D* FIXTURES ON THE IDR. |
| | F) WHEN SUBMITTING METHOD *A* FOR WHOLE BUILDING |
| | COMPLIANCE ALL COMPONENTS WHICH AFFECT THE ENERGY |
| | CONSUMPTION AND EFFICIENCY NEEDS TO BE ENTERED INTO THE |
| | IDR. ( SITE LIGHTING ETC) |
| | 13-400.A |
| | |
| | |
| | |
| | 2) NOTE: **PLANS WERE OK AND STAMPED. |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |