| Plan Review Notes For Permit 09120408 |
| Permit Number |
09120408 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-21 15:38:31 | RESIDENTIAL (R3) REROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 TO MEET THE DESIGN PRESSURES OF SEC. R301 | | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301. ALSO, SPECIFY WHICH BASE SHEET | | | FASTENING OPTION IS GOING TO BE INSTALLED. | | | | | | JULIO GOMEZ | | | COMBINATION COMMERCIAL PLANS EXAMINER | | | (561)805-6712 |
|