| 2009-12-30 16:47:50 | * DENIED REVISION** |
| | |
| | SEE PROVISO NOTES BELOW FROM PREMIT ISSUANCE WHICH ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | |
| | ** PROVISO ** |
| | |
| | ** ALL OF THE FOLLOWING COMMENTS NEED TO BE ADDRESSED |
| | BEFORE ANY FINAL ELECTRICAL INSPECTION. |
| | ** OTHER ITEMS REVISED ON PLANS WHICH ARE NOT PART OF |
| | PROVISO, SHALL BE REVISED AND SUBMITTED BEFORE ROUGH |
| | ELECTRICAL INSPECTION. |
| | **** |
| | *PROVISO IS GIVEN AT THE REQUEST OF THE DESIGNER AND |
| | WILL BE COMPLETELY AT THE RISK OF CONTRACTOR, |
| | ELECTRICAL CONTRACTOR AND DESIGNER OF RECORD. |
| | |
| | 1) NOTE: PLANS NEED TO SHOW ALL CIRCUITING FOR LIGHTING |
| | AND RECEPTACLES. THIS WILL NEED TO BE SUBMITTED AND |
| | COORDINATE WITH PANEL SCHEDULES WHICH HAVE NOT YET BEEN |
| | SUBMITTED AND SHOWN ON RECORD SET OF PLANS. |
| | 408.4,310.16,240.4 ETC |
| | |
| | 2) NOTE: ALL FINAL LOAD CALCULATIONS FOR ALL LIGHTING, |
| | RECEPTACLES AND OTHER LOADS SHALL BE COMPLETED ON |
| | RECORD SET OF PLANS. |
| | PLEASE SEE ALL OF NEC 220 FOR CODES SUCH AS |
| | 220.12,220.14,220.42,220.44 ETC |
| | PLEASE SEE 215.3,230.42 ETC FOR CONTINUOUS LOADS. |
| | |
| | 3) NOTE: PANEL AND TAPPED CONDUCTORS ON THE SECONDARY |
| | SIDE OF COMPUTER TRANSFORMER SHALL MEET 240.21,408.36, |
| | 240.4,310.16 ETC |
| | THE PLANS ARE NOT COMPLETE WITH CONDUCTORS ETC SHOWN |
| | FOR EXISTING. THERE MAY BE CODE COMPLIANCE COMMENTS |
| | WHICH CAN NOT BE REVIEWED OR MADE AT THIS TIME. THIS |
| | MAY CREATE CHANGES NEEDED IN FIELD. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |