| Plan Review Notes For Permit 09120397 |
| Permit Number |
09120397 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-22 16:58:05 | REVISION IS DENIED. | | | | | | 1) BASED ON THE INFORMATION PROVIDED BY THE FIELD | | | INSPECTOR, THE BRANCH PIPING AT THE MAIN DRAINS IS | | | REDUCED TO 2 ". THE REVISION SPECIFIES A 1 HP PUMP WITH | | | A 107 GPM FLOW RATE. THE TOTAL DYNAMIC HEAD IS NOT | | | SPECIFIED. THEREFORE, USING THE 107 GPM THE VELOCITY | | | THROUGH THE 2 " PIPE WILL EXCEED THE 6 FT/SEC MAXIMUM | | | ALLOWED BY CODE. |
|