| Plan Review Notes For Permit 09120349 |
| Permit Number |
09120349 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-01-05 14:13:33 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 CHAPTER 1 | | | FBC-2007 EXISTING BUILDING | | | | | | 1. PER SECTION 401.4 A DESIGN PROFESSIONAL OR OWNER | | | MUST ELECT ONE OR A COMBINATION OF LEVELS OF | | | ALTERATION. | | | | | | 2. PER SECTION 106.3.5.1.3 A WATER ISOMETRIC RISER | | | DIAGRAM IS REQUIRED. PLEASE SUBMIT THE RISER DIAGRAM | | | SHOWING ALL PIPE SIZES, VALVES & (WHERE REQUIRED BY | | | SECTION 604.9), WATER HAMMER ARRESTORS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|