Plan Review Notes
Plan Review Notes For Permit 09120349
Permit Number 09120349
Review Stop M
Sequence Number 1
Notes
Date Text
2009-12-22 15:19:02**PROVISO**
  
 1. REVISE PLAN TO SHOW THE CFM OF THE EXHAUST FAN IN
 ACCORDANCE WITH FBC-M 403.3
  
 2. REVISE PLAN TO SHOW LOCATION OF EXHAUST DISCHARGE IN
 ACCORDANCE WITH FBC-M 401.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved