Plan Review Notes
Plan Review Notes For Permit 09120349
Permit Number 09120349
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-29 13:38:21*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. INDICATE IF THE BUILDING HAS A FIRE ALARM AND/OR
 FIRE SPRINKLER SYSTEM, AND TO WHAT EFFECT WILL THE
 SCOPE OF WORK HAVE ON THE/THESE SYSTEM(S).
  
 3. ON SHEET A-2, ONLY ONE (1) EXIT LIGHT IS SHOWN. SHOW
 THE LOCATION OF ADDITIONAL EXIT LIGHTS AND/OR EMERGENCY
 LIGHTS PERTINENT TO EGRESSING THE BUILDING.
  
 4. SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH
 SATIFY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722