| Plan Review Notes For Permit 09120349 |
| Permit Number |
09120349 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-29 13:38:21 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. INDICATE IF THE BUILDING HAS A FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEM, AND TO WHAT EFFECT WILL THE | | | SCOPE OF WORK HAVE ON THE/THESE SYSTEM(S). | | | | | | 3. ON SHEET A-2, ONLY ONE (1) EXIT LIGHT IS SHOWN. SHOW | | | THE LOCATION OF ADDITIONAL EXIT LIGHTS AND/OR EMERGENCY | | | LIGHTS PERTINENT TO EGRESSING THE BUILDING. | | | | | | 4. SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) WHICH | | | SATIFY THE 75' TRAVEL DISTANCE. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|