| 2009-12-28 13:58:23 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLANS DO NOT CONTAIN ANY SPECIFIC RELEVANT |
| | CODES. ALL PERMIT APPLICATIONS AFTER OCTOBER 1ST, 2009 |
| | ARE REQUIRED TO BE UNDER THE FOLLOWING CODES. |
| | |
| | 2007 FBC W/ 2009 SUPPLEMENTS. |
| | 2006 NFPA-101 |
| | 2008 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | |
| | |
| | PER: FS 553.73, FAC 69A-3.012, 69A-60.004 |
| | |
| | 2) NOTE: PLANS LIST AN ENGINEERING FIRM AS THE |
| | RESPONSIBLE DESIGNERS HOWEVER THE ENGINEER HAS NOT |
| | SIGNED, DATED OR SEALED PLANS. PLEASE REVISE TITLE |
| | BLOCKS, OR HAVE ENGINEER SIGN, DATE AND SEAL PLANS AS |
| | REQUIRED. FS 471.025, FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE SHOW CIRCUITING FOR NEW ELECTRICAL AND |
| | COORDINATE WITH PANEL SCHEDULE. |
| | PLEASE SEE 408.4 OF THE NEC WHICH REQUIRES CIRCUITING |
| | TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | THE USE OF *RECEPTACLES* OR *LIGHTING* IN GENERAL TERMS |
| | IS NOT PERMITTED. PLEASE SEE CODE COMMENTARY WHICH WAS |
| | ACTUALLY REVISED IN THE 2005 NEC. |
| | |
| | 4) NOTE: RISER MENTIONS THE EXISTING FEEDERS ARE RATED |
| | FOR 600AMPS, NEW CONDUCTORS MUST MEET 310.16,240.4. |
| | |
| | 5) NOTE: PLEASE VERIFY WITH FIRE MARSHAL THAT MORE THAN |
| | ONE DISCONNECT WILL BE PERMITTED FOR SINGLE TENANT. |
| | |
| | 6) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 FOR MINIMUM |
| | PRESCRIPTIVE REQUIREMENTS FOR LIGHTING CONTROLS FOR NEW |
| | BEING INSTALLED. THIS WOULD BE ANY NEW LOCATION SUCH AS |
| | NEW BATH. |
| | |
| | 7) NOTE: PLANS SEEM TO INDICATE A NEW TRANSFORMER OF |
| | SOME KIND AND NEW EQUIPMENT HOWEVER NO SPECIFIC DETAIL |
| | AND INFORMATION IS PROVIDED. |
| | 450,240,310, ETC GIVEN IN GENERAL AS THERE IS NO |
| | INFORMATION. |
| | |
| | 8) NOTE: IS THERE ANY FIRE ALARM SYSTEM IN THIS |
| | BUILDING? IS THERE EXISTING OR NEW DEVICES MEETING FBC |
| | 11-4.28.1, .2 AND .3 FOR ADA LOCATED IN SPACE? |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | |