| 2010-01-06 12:18:05 | ZONING HAS ELECTRICAL SITE PLANS FOR COORDINATION |
| | REVIEW. |
| 2010-01-06 12:04:58 | |
| | ** DENIED * |
| | |
| | |
| | 1) NOTE: NEW PROOFING OVEN IN KITCHEN NOT SHOWING GFI |
| | OR GFI PROTECTION ON PANEL SCHEDULE. 210.8B3 ( 2002 |
| | NEC) |
| | |
| | 2) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.16. ( |
| | 2002 NEC) SINCE THESE UNITS FALL UNDER THE DEFINITION |
| | OF A DWELLING UNIT WITH PERMANENT MEANS FOR COOKING ALL |
| | SMALL APPLIANCE LOADS ARE REQUIRED TO BE FIGURED PER |
| | 220.16 BELOW. ALL DE-RATINGS ARE PERMITTED AND MAY BE |
| | ON SOME PANELS SUCH AS B4. |
| | PLEASE BE SURE TO ADJUST LOADS THROUGH TO THE L PANELS, |
| | H PANELS AND SERVICE. |
| | |
| | |
| | 220.16 SMALL APPLIANCE AND LAUNDRY LOADS ??? DWELLING |
| | UNIT. |
| | (A) SMALL APPLIANCE CIRCUIT LOAD. IN EACH DWELLING |
| | UNIT, THE LOAD SHALL BE COMPUTED AT 1500 VOLT-AMPERES |
| | FOR EACH 2-WIRE SMALL-APPLIANCE BRANCH CIRCUIT REQUIRED |
| | BY 210.11(C)(1). WHERE THE LOAD IS SUBDIVIDED THROUGH |
| | TWO OR MORE FEEDERS, THE COMPUTED LOAD FOR EACH SHALL |
| | INCLUDE NOT LESS THAN 1500 VOLT-AMPERES FOR EACH 2-WIRE |
| | SMALL-APPLIANCE BRANCH CIRCUIT. THESE LOADS SHALL BE |
| | PERMITTED TO BE INCLUDED WITH THE GENERAL LIGHTING LOAD |
| | AND SUBJECTED TO THE DEMAND FACTORS PROVIDED IN TABLE |
| | 220.11. |
| | |
| | 3) NOTE: THERE ARE REVISIONS INDICATED WITH CLOUDS ON |
| | SOME SHEETS HOWEVER THERE IS NO ACTUAL CHANGE FROM |
| | PREVIOUS PLANS ON FILE. THERE ARE REVISION DATES ON |
| | TITLE BLOCK WITH NO CHANGES OR PLANS ALREADY ON FILE OR |
| | DATES WHICH ACTUALLY GO BACK BEFORE THE LATEST REVISION |
| | ON FILE. PLEASE SEE EXAMPLES BELOW. |
| | |
| | EXAMPLE: SHEET E301B RIGHT OUTSIDE NEXT TO DRIVE UP |
| | AREA WHICH HAS A CLOUD AROUND THE CIRCUITING TO H1-50. |
| | HOWEVER THIS IS THE SAME ON PLANS ALREADY IN RECORD |
| | FILE SET. |
| | EXAMPLE: PLEASE SEE SHEET E301A ELEVATOR MACHINE ROOM |
| | THERE IS A CLOUD NOTING A REVISION #13, HOWEVER THERE |
| | IS NO CHANGE FROM PREVIOUS PLANS |
| | |
| | ON FILE. |
| | EXAMPLE: SHEET 302 HAS NO CHANGES OR REVISIONS FROM |
| | PLANS ON FILE. |
| | EXAMPLE: SHEET 303 HAS NO CHANGES OR REVISIONS FROM |
| | PLANS ON FILE. LAST REVISION MADE TO SHEET WAS FROM |
| | DECEMBER 2007. |
| | EXAMPLE: SHEET E-401. THE LAST REVISION ON FILE IS |
| | DECEMBER 2007 HOWEVER THERE IS NOW A REVISION #9 |
| | INDICATED AS JULY 2007. THIS DATE PRECEDES THE DECEMBER |
| | DATE? |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | |
| | |
| | |
| | [email protected] |
| | |