| Plan Review Notes For Permit 09120313 |
| Permit Number |
09120313 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-21 10:20:48 | FAILED | | | | | | 1) THE CITYPLACE DRI REQUIRES THAT ALL ROOFTOP | | | MECHANICAL EQUIPMENT BE SCREENED FROM VIEW, THIS | | | INCLUDES EXHAUST FANS/EQUIPMENT. | | | | | | 2) PROVIDE ELEVATION DRAWINGS WITH THE ULTIMATE HEIGHT | | | OF THE EXHAUST FAN FROM THE ROOF. IT APPEARS THAT THE | | | FAN UNIT IS 41.25 INCHES HIGH, BUT IT IS UNCLEAR IF | | | THIS INCLUDES THE STAND (CURB?). ADDITIONALLY, PROVIDE | | | THE HEIGHT OF THE PARAPET THAT SURROUNDS THIS SECTION | | | OF ROOF. NOTE THAT THE EQUIPMENT SHALL NOT EXCEED THE | | | HEIGHT OF THE PARAPET UNLESS ADDITIONAL SCREENING IS | | | PROVIDED. | | | | | | 3) NOTE THAT THE PROVISION OF THE INFORMATION ABOVE MAY | | | RESULT IN ADDITIONAL COMMENTS OR THE NEED FOR A MINOR | | | PLANNED DEVELOPMENT AMENDMENT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | |
|