| 2009-12-29 13:49:19 | |
| | ** DENIED REVIEW ** |
| | |
| | **REVISION |
| | ***IMPORTANT** A SEPARATE PROVISO WILL BE DONE FOR ALL |
| | CIRCUITING AND PANEL SCHEDULES. HOWEVER CODE COMPLIANCE |
| | FOR LOADS ON BRANCH CIRCUITS, PANELS, CIRCUITING, OVER |
| | CURRENT PROTECTION AND WIRING CAN NOT BE REVIEWED AT |
| | THIS TIME. ALL CIRCUITING AND WIRING ON-SITE WILL BE AT |
| | THE COMPLETE RISK OF DESIGNER AND CONTRACTOR. THIS IS |
| | PER THE REQUEST OF THE DESIGNER. |
| | |
| | |
| | 1) NOTE: WHEN SUBMITTING PLANS PLEASE BE SURE TO SUBMIT |
| | TWO COMPLETE SETS. ONE SET MISSING ELECTRICAL PAGES. |
| | |
| | 2) NOTE: CODE COMPLIANCE FOR LIGHTING CALCULATIONS CAN |
| | NOT BE VERIFIED AT THIS TIME. THERE IS LIGHTING |
| | FIXTURES NOT IDENTIFIED ON PLANS AND ON FIXTURE LEGEND. |
| | FOR EXAMPLE: ELECTRICAL PLANS DO NOT CONTAIN LIGHTING |
| | PERFORMANCE CALCULATIONS. THESE WERE LOCATED ON THE |
| | SHEET 1.2A HOWEVER ONLY FOR FIRST FLOOR LIGHTING. WHERE |
| | IS THE SECOND FLOOR LIGHTING PLANS FOR IDENTIFICATION |
| | AND CALCULATIONS? THE SECOND FLOOR LIGHTING PLANS ON |
| | ELECTRICAL SHEETS DO NOT CONTAIN FIXTURE |
| | IDENTIFICATION. |
| | FOR EXAMPLE: PLEASE SEE LIGHTING ON SHEET 1.2A AS THERE |
| | ARE FIXTURES SUCH AS THE 2X4 LAY-INS WHICH ARE |
| | IDENTIFIED WITH A LETTER *D* FOR THE FIXTURE YET THE |
| | FIXTURE LEGEND DOES NOT HAVE ANY FIXTURE *D*. |
| | FOR EXAMPLE: THE SECOND FLOOR LIGHTING PLANS DO NOT |
| | HAVE FIXTURES IDENTIFIED. THE FIXTURES SUCH AS THE |
| | 2LIGHT FLUORESCENT IN COOLERS ARE ONLY BEING SHOWN AS |
| | 2-LT FIXTURES. WHAT KIND OF TWO LIGHT FIXTURES? MAXIMUM |
| | WATTAGE? THESE CAN NOT BE ASSUMED. PLANS DO STATE ON |
| | 1.2A THE PF OF 1.0 HOWEVER IF THE FIXTURE WATTAGE IS |
| | NOT LISTED THIS CAN NOT BE FIGURED. |
| | WHERE ARE THE TRACK LIGHTS AS SHOWN ON THE FIXTURE |
| | LEGEND? COULD NOT LOCATE THESE ON PLANS. THE FIXTURE IS |
| | SHOWN AS TYPE K AND THE ONLY LOCATION ON SHEET 1.2A IS |
| | IN THE CORNER OF MAIN EATING AREA. THIS SAME AREA ON |
| | E-SHEETS APPEAR TO BE A KEY PAD?? |
| | PLEASE BE SURE TO REMEMBER IF COVE LIGHTING IS TRACK |
| | TYPE, THEN 30VA MINIMUM IS REQUIRED TO BE USED. |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE COMPLETE AND |
| | SUBMIT. |
| | |
| | 3) NOTE: PLEASE COMPLETE CONTROLS FOR ALL LIGHTS ON |
| | PLANS. SOME AREAS SUCH AS KITCHEN LIGHTING ON 2.0E AND |
| | COOLER LIGHTS ON 2.1E DO NOT HAVE ANY CONTROLS? |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 4) NOTE: LIGHTING IN STAIRWAYS MUST MEET MINIMUM LEVELS |
| | FOR LIFE SAFETY. THE TWO MR-16 50WATT FIXTURES AS SHOWN |
| | DO NOT PROVIDED ENOUGH LIGHT FOR 10FT CANDLES. |
| | NFPA-101 7.8.1.3. |
| | WITH THE SCOPE OF WORK BEING DONE AT THIS LOCATION THIS |
| | WILL BE REQUIRED TO MEET CURRENT CODE. |
| | |
| | 5) NOTE: NEW BAR AREAS WHERE SINKS ARE LOCATED WILL BE |
| | REQUIRED TO HAVE RECEPTACLES GFI/GFI PROTECTED. 210.8B2 |
| | PLANS CONTAIN NOTES FOR FIRST FLOOR KITCHEN AND BAR |
| | AREAS ALONG WITH GFI IDENTIFICATION HOWEVER NOT SECOND |
| | FLOOR. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | |
| | |
| | |
| | |