Plan Review Notes
Plan Review Notes For Permit 09120310
Permit Number 09120310
Review Stop E
Sequence Number 2
Notes
Date Text
2009-12-29 13:49:19 
 ** DENIED REVIEW **
  
 **REVISION
 ***IMPORTANT** A SEPARATE PROVISO WILL BE DONE FOR ALL
 CIRCUITING AND PANEL SCHEDULES. HOWEVER CODE COMPLIANCE
 FOR LOADS ON BRANCH CIRCUITS, PANELS, CIRCUITING, OVER
 CURRENT PROTECTION AND WIRING CAN NOT BE REVIEWED AT
 THIS TIME. ALL CIRCUITING AND WIRING ON-SITE WILL BE AT
 THE COMPLETE RISK OF DESIGNER AND CONTRACTOR. THIS IS
 PER THE REQUEST OF THE DESIGNER.
  
  
 1) NOTE: WHEN SUBMITTING PLANS PLEASE BE SURE TO SUBMIT
 TWO COMPLETE SETS. ONE SET MISSING ELECTRICAL PAGES.
  
 2) NOTE: CODE COMPLIANCE FOR LIGHTING CALCULATIONS CAN
 NOT BE VERIFIED AT THIS TIME. THERE IS LIGHTING
 FIXTURES NOT IDENTIFIED ON PLANS AND ON FIXTURE LEGEND.
 FOR EXAMPLE: ELECTRICAL PLANS DO NOT CONTAIN LIGHTING
 PERFORMANCE CALCULATIONS. THESE WERE LOCATED ON THE
 SHEET 1.2A HOWEVER ONLY FOR FIRST FLOOR LIGHTING. WHERE
 IS THE SECOND FLOOR LIGHTING PLANS FOR IDENTIFICATION
 AND CALCULATIONS? THE SECOND FLOOR LIGHTING PLANS ON
 ELECTRICAL SHEETS DO NOT CONTAIN FIXTURE
 IDENTIFICATION.
 FOR EXAMPLE: PLEASE SEE LIGHTING ON SHEET 1.2A AS THERE
 ARE FIXTURES SUCH AS THE 2X4 LAY-INS WHICH ARE
 IDENTIFIED WITH A LETTER *D* FOR THE FIXTURE YET THE
 FIXTURE LEGEND DOES NOT HAVE ANY FIXTURE *D*.
 FOR EXAMPLE: THE SECOND FLOOR LIGHTING PLANS DO NOT
 HAVE FIXTURES IDENTIFIED. THE FIXTURES SUCH AS THE
 2LIGHT FLUORESCENT IN COOLERS ARE ONLY BEING SHOWN AS
 2-LT FIXTURES. WHAT KIND OF TWO LIGHT FIXTURES? MAXIMUM
 WATTAGE? THESE CAN NOT BE ASSUMED. PLANS DO STATE ON
 1.2A THE PF OF 1.0 HOWEVER IF THE FIXTURE WATTAGE IS
 NOT LISTED THIS CAN NOT BE FIGURED.
 WHERE ARE THE TRACK LIGHTS AS SHOWN ON THE FIXTURE
 LEGEND? COULD NOT LOCATE THESE ON PLANS. THE FIXTURE IS
 SHOWN AS TYPE K AND THE ONLY LOCATION ON SHEET 1.2A IS
 IN THE CORNER OF MAIN EATING AREA. THIS SAME AREA ON
 E-SHEETS APPEAR TO BE A KEY PAD??
 PLEASE BE SURE TO REMEMBER IF COVE LIGHTING IS TRACK
 TYPE, THEN 30VA MINIMUM IS REQUIRED TO BE USED.
 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE COMPLETE AND
 SUBMIT.
  
 3) NOTE: PLEASE COMPLETE CONTROLS FOR ALL LIGHTS ON
 PLANS. SOME AREAS SUCH AS KITCHEN LIGHTING ON 2.0E AND
 COOLER LIGHTS ON 2.1E DO NOT HAVE ANY CONTROLS?
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: LIGHTING IN STAIRWAYS MUST MEET MINIMUM LEVELS
 FOR LIFE SAFETY. THE TWO MR-16 50WATT FIXTURES AS SHOWN
 DO NOT PROVIDED ENOUGH LIGHT FOR 10FT CANDLES.
 NFPA-101 7.8.1.3.
 WITH THE SCOPE OF WORK BEING DONE AT THIS LOCATION THIS
 WILL BE REQUIRED TO MEET CURRENT CODE.
  
 5) NOTE: NEW BAR AREAS WHERE SINKS ARE LOCATED WILL BE
 REQUIRED TO HAVE RECEPTACLES GFI/GFI PROTECTED. 210.8B2
 PLANS CONTAIN NOTES FOR FIRST FLOOR KITCHEN AND BAR
 AREAS ALONG WITH GFI IDENTIFICATION HOWEVER NOT SECOND
 FLOOR.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  
  
  
  