Plan Review Notes
Plan Review Notes For Permit 09120310
Permit Number 09120310
Review Stop M
Sequence Number 1
Notes
Date Text
2009-12-23 10:43:14REVIEW #: 1ST (REVISION EXPANDING SCOPE TO INCLUDE
 MECH.)
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE 3.2M SHOWS A RETURN AIR GRILL IN THE KITCHEN.
 AS THIS SYSTEM IS NOT DEDICATED TO THE KITCHEN AREA,
 RETURN AIR FROM THE KITCHEN IS PROHIBITED IN ACCORDANCE
 WITH FBC-M 407.1. HOOD EXHAUST AND MAKE-UP AIR SYSTEMS
 SHALL BE BALANCED TO MAINTAIN PRESSURE DIFFERENTIAL
 REQUIREMENTS AS STATED IN FBC-B 13-409.1.ABC.3.6.1.
  
 2. PAGE 3.2M SHOWS A TYPE B GRILL BEHIND THE BAR
 PROVIDING 200 CFM SUPPLY. BASED ON THE "CEILING OUTLET
 SCHEDULE," THIS GRILL IS CAPABLE OF PROVIDING A MAXIMUM
 150 CFM. COORDINATE FLOOR PLANS TO FACILITATE A PROPER
 AIR BALANCE IN ACCORDANCE WITH FBC-M 603.1.
  
 3. PAGE 3.2M AND 3.3M EACH CONTAIN NOTES DESCRIBING THE
 PROPOSED WORK AS BEING "AS-BUILT HVAC 04NOV09." PLEASE
 CLARIFY HOW AS-BUILT DRAWINGS ARE BEING PRODUCED PRIOR
 TO ISSUANCE OF A MECHANIACL PERMIT FOR THE PROPOSED
 SCOPE OF WORK. A PERMIT SHALL BE SECURED PRIOR TO THE
 COMMENCEMENT OF ANY REGULATED WORK IN ACCORDANCE WITH
 FBC-B 105.1.
  
 4. PAGE 3.3M: RETURN AIR GRILL DESIGNATION AND CFM IS
 MISSING FOR RTU 4. PROVIDE MISSING INFORMATION IN
 ACCORDANCE WITH FBC-M 603.1.
  
 5. PAGE 3.2M SHOWS THE 12.5 TON RTU 1 AS EXISTING WHILE
 THE "SCOPE OF WORK" NOTES ON PAGE 3.3M CALL FOR RTU 1
 TO BE REPLACED WITH NEW. PLEASE COORDINATE NOTES AND
 FLOR PLANS TO ACCURATELY REFLECT THE PROPOSED SCOPE OF
 WORK IN ACCORDANCE WITH FBC-B 106.1.
  
 6. NEW RTU 1 SHALL BE PROVIDED WITH A MOTORIZED DAMPER
 AND SHUTOFF DAMPER CONTROLS ON THE OUTSIDE AIR INTAKE
 PER FBC-B 13-409.1.ABC.3.3.
  
 7. PAGE 3.3M SHOWS A 10" ROUND RETURN AIR TRANSFER DUCT
 FROM THE PREP/STORAGE ROOM. THIS TRANSFER ALSO CARRIES
 THE RETURN AIR FROM THE ADJACENT OFFICE. SIZE THIS
 TRANSFER DUCT TO MEET THE BALANCED RETURN EXCEPTIONS
 UNDER FBC-M 601.4 OR A FIELD TEST WILL BE REQUIRED
 PRIOR TO FINAL INSPECTION TO VERIFY PRESSURE
 DIFFERENTIAL OF 0.01 INCHES W/C.
  
 8. SEPARATE PLANS AND PERMIT APPLICATION SHALL BE
 SUBMITTED FOR PIZZA OVEN HOOD SYSTEM.
 NOTE: ARE ANY PROVISIONS BEING MADE FOR
 MAKEUP/COMBUSTION AIR FOR THE NEW PIZZA OVEN?
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]