2009-12-16 18:22:56BUILDING PLAN REVIEW
 PERMIT: 08080193/
 REVISION 09120310
  
 ADD: 118 S CLEMATIS ST
 CONT: FIVE STAR CONSTRUCTION
 TEL: (561)436-8508
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW
  
 BUILDING PROVISO :
  
  
 1) SHEET 1.0A & 1.1A TWO FIRE SPRINKLER HEADS TO BE
 INSTALLED AT WITHIN 1???-0??? OF TEMPERED GLAZING IN
 THE 1 HR RATED STAIRWELL FIRST FLOOR GLAZING AND 2ND
 FLOOR GLAZING, A TOTAL OF FOUR SPRINKLER HEADS PER
 JOBSITE MEETING.
  
  
 2) BOTH DOOR AND WINDOW FRAMES WITHIN THE ONE-HOUR
 RATED STAIRWAY WILL NEED TO BE 45 MINUTE RATED PER
 TABLE 715.4 AND LABELED PER 715.4.5.4.
  
  
  
 3) SHEET 1.3A, NEW EXTERIOR STAIRWELL DOOR NEEDS
 PRODUCT APPROVALS TO BE SUBMITTED BEFORE BUCK
 INSPECTION. COMPONENTS AND CLADDING 1609.1.2.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026