| 2009-12-21 17:01:01 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE CLASSIFICATION OF WORK IS INCORRECT. THE PLANS |
| | AND APPLICATION INDICATE THAT THE SCOPE OF WORK IS TO |
| | BUILD A NEW GAZEBO. NOT AN ADDITION OR A LEVEL 3 |
| | ALTERATION TO AN EXISTING STRUCTURE. PLEASE CORRECT. |
| | |
| | 2) SPECIFY THE WIND DESIGN INFORMATION ON THE PLANS. |
| | FBC R301.2.1 |
| | |
| | 3) SPECIFY THE LIVE AND DEAD LOADS FOR THE ROOF AND |
| | FLOOR ON THE PLANS. FBC R301.4, 301.5 AND 301.6. |
| | |
| | 4) SPECIFY THE HANGERS THAT WILL BE USED TO ATTACH THE |
| | 2 X 6 FLOOR JOISTS TO THE 2 X 6 BAND. R301.1 |
| | |
| | 5) EVALUATE THE FLOOR LOADS WITH THE JOIST SIZE AND |
| | SPAN, AS WELL AS, TYPE OF LUMBER ( PLEASE SPECIFY) TO |
| | DETERMINE THAT THEY ARE ADEQUATE. R301.1 |
| | |
| | 6) EVALUATE THE SPAN OF SINGLE 2 X 6 BAND TO DETERMINE |
| | THAT IT IS CAPABLE OF SUPPORTING THE FLOOR LOADS. |
| | R301.1 |
| | |
| | 7) THE PLANS SPECIFY A 2 X 6 GUARDRAIL WITH A HEIGHT OF |
| | 5'-3" AND A 2 X 4 RAILING @ 2' O.C. IS THIS CORRECT? |
| | PLEASE PROVIDE A DETAILED DRAWING THAT CLARIFIES THE |
| | DESIGN AND ATTACHMENT. FBC R 312 |
| | |
| | 8) THE PLANS HAVE A DETAIL OF THE DOUBLE 2 X 8 HEADER |
| | ON A 4 X 4 POST WITH A USP KCC-4 POST CAP. PLEASE |
| | CLARIFY HOW THE 2 X 8 HEADERS WILL BE CONNECTED |
| | TOGETHER AT THE TOP OF THE POST. PROVIDE DETAIL. R601.2 |
| | |
| | 9) A SIMPSON HETA 20 CONNECTOR IS SPECIFIED AT THE ROOF |
| | TRUSSES. THIS IS AN EMBED TYPE OF CONNECTOR USED WITH |
| | CONCRETE BEAMS. PLEASE CORRECT. R802.1.6.5 |
| | |
| | 10) A SIMPSON SWH 28-2 HANGER IS SPECIFIED AT THE |
| | DOUBLE 2 X 8S. I COULD NOT FIND THIS CONNECTOR IN THE |
| | SIMPSON CATALOG. PLEASE CLARIFY. R802.1.6.5 |
| | |
| | 11) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | SIMPSON AND USP CONNECTORS AS REQUIRED BY DCA RULE |
| | 9B-72 OR SPECIFY THE FLORIDA PRODUCT APPROVAL NUMBERS |
| | FOR EACH OF THEM ON THE PLANS. |
| | |
| | 12) SHOW COMPLIANCE WITH FBC R 803.2.3.1 FOR SHEATHING |
| | FASTENING ON THE PLANS, WHICH REQUIRES 8D RING SHANK |
| | NAILS. |
| | |
| | 13) THE VALUE OF THE WORK IS LOW AND HAS BEEN ADJUSTED |
| | TO $ 4300.00 BASED ON ICC VALUATION TABLES. |
| | |