| Date |
Text |
| 2010-02-01 16:59:03 | REVISION TO 09100241 |
| | |
| | REVISED SHEETS A2.1, A3.1, A4.1, A5.2 AND A5.3 ARE OK. |
| | |
| | STORM PANEL SUBMITTALS ARE DENIED BY BUILDING. |
| | |
| | 1) THE STORM PANEL INSTALLATION SCHEDULE IS NOT |
| | COMPLETED. THE WALL PRESSURES THAT ARE SPECIFIED ON THE |
| | FORM ARE FOR OPENINGS OF 20 SQUARE FEET. |
| | |
| | 2) THE WINDOW SIZES ON THE STORM PANEL SCHEDULE DO NOT |
| | CORRESPOND WITH THE ONES ON THE PLANS (A2.1). PLEASE |
| | CORRECT. |
| | |
| | 3) THE LETTER TO THE BUILDING OFFICIAL REQUESTING THE |
| | USE OF STORM PANELS IS REQUIRED TO BE FROM THE BUSINESS |
| | OWNER. IN ADDITION TO THE STORE OWNER, SPECIFY AN |
| | ALTERNATE PERSON THAT WILL BE RESPONSIBLE FOR |
| | INSTALLING THE STORM PANELS IF THE OWNER IS NOT |
| | AVAILABLE. |
| | |
| | 4) THE LETTER INDICATES THAT THE STORM PANELS WILL BE |
| | STORED IN THE ATTIC. PLEASE SPECIFY THE SIZE OF THE |
| | ATTIC ACCESS OPENING. |
| | |
| | 5) THE PRODUCT APPROVAL DRAWINGS THAT WERE SUBMITTED |
| | (08-142) ARE FOR 24GA. STEEL PANELS, WHICH WILL ADD A |
| | SUBSTANTIAL LIVE LOAD TO THE ATTIC. SUBMIT DETAILS FOR |
| | THE STRUCTURE OF THE CEILING SHOWING THAT THE LOADS |
| | WILL BE SAFELY SUPPORTED. |
| | |
| | 6) THE LETTER ALSO NEEDS TO STATE THAT THE TOOLS AND |
| | EQUIPMENT (SUCH AS LADDERS) REQUIRED FOR INSTALLING THE |
| | PANELS WILL ALSO BE STORED ON SITE. |
| | |
| | 7) PLEASE CLARIFY THE PURPOSE OF THE FLEMING STEEL DOOR |
| | AND FRAME UL FOLLOW-UP INFORMATION THAT WAS ATTACHED TO |
| | THE STORM PANEL SUBMITTAL. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |