| 2011-01-24 14:10:00 | MASTER PLAN (MODEL B) FOR NEW SINGLE FAMILY RESIDENCE |
| | (R3), BUILDING REVIEW SECOND CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | 2- SHEET A/A1.0: LEAVE LOCATION MAP BOX IN BLANK. THIS |
| | IS APPLICATION FOR MASTER NOT FOR A SPECIFIC LOT. |
| | |
| | 3- ALL DRAWINGS HAVE THE LOT 42 ON THE TITLE BLOCK. |
| | DELETE AS REQUIRED. |
| | |
| | 4- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS |
| | SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT |
| | NOA. |
| | |
| | B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED |
| | EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE |
| | REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE. |
| | |
| | C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON |
| | JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR |
| | FUTURE SUBMITTAL AFTER THIS DATE. |
| | |
| | D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA |
| | 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10 |
| | WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS |
| | GOING TO BE USED. |
| | |
| | E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS. (REPEAT |
| | COMMENT). |
| | |
| | F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. (REPEAT |
| | COMMENT). |
| | |
| | G) PRECAST LINTELS AS SPECIFIED ON PLANS. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | H) STORM SHUTTERS. COORDINATE WITH ITEM # 4D ABOVE. AND |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON |
| | SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR |
| | TYPE AND SPACING. |
| | |
| | I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF |
| | PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 5- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. THIS |
| | APPLIES TO NOA'S NO SUBMITTED YET. |
| | |
| | 6- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO |
| | EXPOSURE "C" BUT THE DOORS AND WINDOWS DESIGN PRESSURES |
| | ON SHEETS A-3.0, A-4.0, A-5.0 AND A-7.0 WERE NOT |
| | CHANGED TO REFLECT EXPOSURE "C". |
| | |
| | 7- TRUSS PACKAGE: |
| | A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO |
| | EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL |
| | TRUSSES ACCORDINGLY. |
| | |
| | B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION, |
| | INCLUDING THE ARCHITECT OF RECORD INFORMATION. |
| | |
| | C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT |
| | COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| | |
| | 8- REVISED SHEET A-2.0: |
| | A) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFIES 10 |
| | MIL VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6 |
| | MIL VAPOR BARRIER. REVISE AS REQUIRED TO MATCH. |
| | |
| | B) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE |
| | ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | C) REVISE NOTE REGARDING TRUSS ANCHORS. USING SIMPSON |
| | NOT USP, AND REFER TO CORRECT SHEET. |
| | |
| | 9- SHEET A-7.0: CLARIFY NOTE ON FRONT ELEVATION |
| | REGARDING DECORATIVE LOUVER. THERE IS NOT LOUVER SHOWN |
| | ON THE ELEVATION. |
| | |
| | 10- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS |
| | CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1. |
| | |
| | 11- SHEET A-6.0: |
| | A) COORDINATE DETAIL 4/A-6.0 WITH FASTENERS SPECIFIED |
| | ON STRUCTURAL CONNECTOR SCHEDULE. REVISE TYPE OF |
| | FASTENERS TO MATCH. |
| | |
| | B) FASTENER SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED |
| | BECAUSE IT DOESN'T PROVIDE ANY UPLIFT. SEE SIMPSON |
| | CATALOG. REVISE AS REQUIRED AND COORDINATE DETAIL AND |
| | TRUSS ANCHOR SCHEDULE |
| | |