| 2009-12-22 15:55:29 | DENIED |
| | REFERENCE: |
| | FBC-2007 RESIDENTIAL |
| | FBC-2007 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT A1.0 INDICATES THE DESIGN TO BE PER FBC-2004. |
| | ALL PLANS SUBMITTED FOR PERMIT AFTER MARCH 1, 2009 |
| | SHALL BE DESIGNED TO THE FBC-2007 EDITION WITH 2009 |
| | SUPPLEMENTALS. PLEASE CORRECT CODE REFERENCES. SECTION |
| | 106.1.1. |
| | |
| | 2. ALL SHEETS DESIGNED BY AN ARCHITECT OR ENGINEER |
| | SHALL BE SIGNED, SEALED & DATED PER CHAPTERS 481 & 471 |
| | OF THE FLORIDA STATUTES AND SECTION 106.1. |
| | |
| | 3. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION. PLEASE INDICATE THE |
| | ADDRESS OF THE RESIDENCE ON THE TITLE BLOCK OF EACH |
| | SHEET. SECTION 106.1.1. |
| | |
| | 4. SHT P2.01 GENERAL PLUMBING NOTES #7 INDICATES A |
| | 1-1/4 INCH METER AND A 1-1/4 INCH WATER SERVICE WITH |
| | GATE VALVE AT THE HOUSE. PER TABLE 603.1 18 FIXTURE |
| | UNITS OR LESS ONLY REQUIRES A 5/8 INCH METER AND 3/4 |
| | INCH WATER SERVICE. THE TOTAL FIXTURE UNITS FOR THE |
| | RESIDENCE IS ONLY 14. PLEASE CLARIFY IF THE METER AND |
| | GATE VALVE INDICATED AS WELL SUB-NOTES A THRU E ARE |
| | REQUIRED FOR THIS RESIDENCE. |
| | |
| | 5. SHT P2.01 GENERAL PLUMBING NOTES #8 INDICATES AIR |
| | CHAMBERS AT EACH FIXTURE. AIR CHAMBERS ARE NOT APPROVED |
| | AND SHALL BE DELETED. PDI-WH 201. |
| | |
| | 6. SHT P2.01 SANITARY RISER DIAGRAM. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL CONNECT TO A BRANCH |
| | DRAIN OR DRAINAGE STACK A MINIMUM OF 3 INCHES IN |
| | DIAMETER. SECTION 406.3/P2718.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |