Plan Review Notes
Plan Review Notes For Permit 09120236
Permit Number 09120236
Review Stop B
Sequence Number 1
Notes
Date Text
2009-12-29 09:56:25****ISSUED WITH PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. THE APPLICATION STATES: "5/8" DRYWALL AND INSULATE
 1ST FLOOR." PROVIDE A MORE COMPLETE SPECIFICATION FOR
 THE WORK INCLUDING SPECIFICATION FOR INSULATION FBC CH
 13 (TYPE OF INSULATION AND R VALUE), DRYWALL ON WALLS
 OR CEILINGS OR BOTH? PROVIDE TOTAL SQUARE FOOT AREA FOR
 EACH, FLOOR PLAN MAY BE REQUIRED (SEE ITEM 6).
  
 2. DOES THIS STRUCTURE HAVE ONE OR TWO UNITS? PAPA
 RECORDS SHOW TWO UNITS; PLEASE INCORPORATE THE
 REQUESTED INFORMATION INTO THE PLAN. IF THE FIRST AND
 SECOND FLOORS ARE DIFFERENT UNITS, FIRE SEPARATION IS
 REQUIRED (FBC R317.1).
  
 3. THE APPLICATION STATES THAT DRYWALL/INSULATION IS ON
 THE FIRST FLOOR, NO INFORMATION PROVIDED REGARDING
 LOCATION OF STRUCTURAL ALTERATION (FIRST OR SECOND
 FLOOR). PLEASE REVISE.
  
 4. FBC R313.2.1, INTERCONNECTED HARD WIRED SMOKE ALARMS
 REQUIRED UNLESS EXEMPTED, SEE FBC R313.2.1. SEPARATE
 PERMIT REQUIRED FOR ELECTRIC WORK.
  
 5. DOES THE FIRST FLOOR INCLUDE AN ATTACHED GARAGE OR
 FOSSIL FUEL BURNING APPLIANCE AND A BEDROOM, FBC
 R313.4? CARBON MONOXIDE ALARM MAY BE REQUIRED (SEPARATE
 PERMIT REQUIRED FOR ELECTRIC WORK).
  
 6. PROVIDE A REASONABLE VALUE FOR THE WORK PROPOSED OR
 PROVIDE A COST BREAKDOWN. VALUE APPEARS LOW; THIS
 SHOULD INCLUDE MARKET-VALUE LABOR AND MATERIALS.
  
  