| Notes |
| Date |
Text |
| 2009-12-15 14:21:01 | MECHANICAL PROVISO: MASTER SUITE, 14???X14??? MINIMUM | | | TRANSFER GRILLE. | | | PLEASE SEE SECTION 601.4(2) TRANSFER GRILLES SHALL USE | | | 50 SQUARE INCHES (OF GRILLE AREA) TO 100 CFM (OF SUPPLY | | | AIR) FOR SIZING THROUGH-THE-WALL TRANSFER GRILLES AND | | | USING AN UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO | | | ACHIEVE PROPER RETURN AIR BALANCE. | | | | | | |
|