| Plan Review Notes For Permit 09120136 |
| Permit Number |
09120136 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-22 12:06:15 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. A PERMIT SHALL NOT BE ISSUED UNTIL FEES | | | AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE | | | BEEN PAID. 108.1 FBC.. | | | | | | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 | | | RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1). LOCATE SAME ON PLANS. | | | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME, ALL SHEETS, PER | | | 106.1.3.FBC. | | | | | | 5} AN ELECTRICAL PERMIT IS REQUIRED PER 105.1 FBC AS | | | AMENDED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|