2009-12-16 17:01:072007 FBC W/2009 REVISIONS
 BATHROOM ADDITION
  
 DENIED BY BUILDING
  
 1) THE SCOPE OF WORK THAT IS SHOWN ON THE DRAWINGS THAT
 WERE SUBMITTED IS FOR AN ADDITION TO INCREASE THE SIZE
 OF THE BATHROOM. THE PERMIT TYPE NEEDS TO BE CHANGED TO
 ADDITION SO THAT THE APPROPRIATE SUB-PERMITS, REVIEWS,
 AND INSPECTIONS WILL BE ASSIGNED.
  
 2) THE VALUE OF THE WORK LISTED ON THE APPLICATION FORM
 IS TOO LOW. IT SHOULD BE INCREASED TO A MINIMUM OF
 $3500.00 PER CURRENT ICC BUILDING VALUATION DATA.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) SPECIFY THE WINDSPEED AND WINDLOAD DESIGN
 INFORMATION ON THE PLANS. FBC R301.2.1
  
 5) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 SHINGLES, WINDOW AND IMPACT PROTECTION (STORM PANELS).
 FAC RULE 9B-72.
  
 6) SPECIFY THE SIZE AND TYPE (SINGLE HUNG, ETC.) OF THE
 BATHROOM WINDOW ON THE PLANS. THE BATHROOM WINDOW IS
 REQUIRED HAVE SAFETY GLAZING BY FBC R308.4.
  
 7) SPECIFY THE WALL AND CEILING INSULATION R-VALUES ON
 THE PLANS AS REQUIRED BY FBC R N1100.B
  
 8) SPECIFY THE TERMITE PROTECTION REQUIRED BY R320 ON
 THE PLANS.
  
 9) SPECIFY THE SIZE OF THE FOOTING, MINIMUM DEPTH AND
 THE NUMBER AND SIZE OF THE STEEL REINFORCING BARS ON
 THE PLANS. SEE FBC R403
  
 10) SPECIFY THE THICKNESS OF THE CONCRETE SLAB AND THE
 REQUIRED VAPOR RETARDER ON THE PLANS. SEE FBC R 506.
  
 11) SPECIFY THE SIZE OF WOOD HEADER ABOVE THE WINDOW.
 R603.6
  
 12) SHOW THE SIZE AND STEEL REINFORCEMENT FOR THE BOND
 BEAM AT THE TOP OF THE MASONRY KNEE-WALL. R609.2
  
 13) SPECIFY THE SIZE AND SPACING OF THE VERTICAL
 REINFORCING BARS IN THE MASONRY KNEE-WALL. R609.3
  
 14) SPECIFY THE ANCHORS AND SPACING FOR THE CONNECTION
 OF THE WOOD FRAME WALL TO THE MASONRY KNEE-WALL. R601.2
  
 15) SPECIFY THE TYPE OF LUMBER FOR THE RAFTERS. IF NOT
 #2 SOUTHERN YELLOW PINE (SYP) OR OTHER WOOD WITH
 SPECIFIC GRAVITY GREATER THAN 0.49 THEN THE FASTENER
 SPACING FOR THE ROOF SHEATHING IS REQUIRED TO BE 4 "
 O.C. IN ROOF ZONE 3 AND 6" O.C. IN THE OTHER ZONES. FBC
 R803.2.3.1.
  
 16) SPECIFY 8D RING SHANK NAILS FOR THE ROOF SHEATHING
 FASTENERS AS REQUIRED BY FBC R803.2.3.1.
  
 17) SPECIFY THE ROOF SLOPE AND ATTIC VENTILATION
 REQUIRED BY FBC R806.1.
  
 18) SHOW COMPLIANCE WITH FBC R703.6.3 WHICH REQUIRES A
 BOND BREAK BETWEEN THE STUCCO AND THE WATER-RESISTIVE
 BARRIER OVER THE FRAME WALL SHEATHING.
  