| 2009-12-16 14:11:40 | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1. |
| | |
| | THIS PLAN IS BEING PASSED TO FACILITATE THE START OF |
| | THIS PROJECT, THE PLANS HOWEVER ARE DEFICIENT, AND THE |
| | FOLLOWING ITEMS NEED CORRECTING: |
| | |
| | COMMENTS RELATING TO SHEET E-3 |
| | |
| | 1} THE SMOKE ALARMS ARE SHOWN ON CIRCUIT A-29 WHICH IS |
| | LABELED AS AHU-3 IN THE PANEL SCHEDULE. NOTE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED PER |
| | 313.2.1 TO EXISTING ALARMS AS WELL. CIRCUIT B-26 IS |
| | LABELED SMOKE DETECTOR. |
| | |
| | 2} CIRCUIT B-15 MUST BE A SMALL APPLIANCE CIRCUIT PER |
| | 210.52(B)(1) "RECEPTACLE OUTLETS SERVED IN THE KITCHEN, |
| | PANTRY, BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF |
| | A DWELLING UNIT, THE TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY |
| | 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE |
| | OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS |
| | COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR |
| | REFRIGERATION EQUIPMENT." THE CIRCUIT IS LISTED AS 20 |
| | AMP IN THE PANEL SCHEDULE, BUT IS LABELED AS " GENERAL |
| | USE".TO AVOID CONFUSION IN THE FIELD CHANGE TO |
| | BREAKFAST ROOM OR SMALL APPLIANCE.ALSO ONE RECEPTACLE |
| | ON THAT CIRCUIT IS IN THE KITCHEN WHICH IS NOT A |
| | VIOLATION AS LONG AS IT IS SMALL APPLIANCE. |
| | |
| | 3} THE TRASH COMPACTOR SHOWN ON SHEET A401 IS NOT |
| | CIRCUITED IN THE ISLAND AND IS NOT LISTED IN THE PANEL |
| | SCHEDULE OR THE LOAD CALCULATION. CORRELATE SAME. |
| | |
| | COMMENTS RELATING TO SHEET E-5:ELECTRICAL RISER |
| | DIAGRAM. |
| | |
| | 3} THE #4 CU GROUND RAN WITH THE FEEDERS FROM THE METER |
| | TO THE FIRST MEANS OF DICONNECT (PANEL "A") CREATES A |
| | PARALLEL PATH TO GROUND WITH THE NEUTRAL AND MUST BE |
| | REMOVED. AN ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE |
| | TO BE RAN FROM THE FIRST MEANS OF DISCONNECT. 250.6. |
| | 250.24 (A)(5) |
| | |
| | 4} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. THIS IS |
| | BEING ASED FOR DUE TO RELOCATION OF THE SERVICE. |
| | |
| | 5} AN INTERSYSTEM BONDING TERMINAL PER 250.94 WILL BE |
| | REQUIRED AT THE RELOCATED SERVICE. |
| | |
| | PLEASE RESUBMIT A REVISION SHOWING ACTUAL CONDITIONS |
| | PRIOR TO CALLING ROUGH ELECTRICAL INSPECTION. THE |
| | REVIEWED PLAN MUST BE ON THE JOB SITE AT TIME OF |
| | INSPECTION. ALLOW AT LEAST ONE WEEK (PER TRADE) FOR |
| | PLAN REVIEW. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |