| Date |
Text |
| 2009-12-16 15:20:34 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | ***NOTE: PLEASE MAKE SURE ALL THE INFORMATION IS |
| | PROVIDED AND FORM IS PROPERLY SIGNED AND DATED BY THE |
| | REQUIRED PARTIES. |
| | |
| | 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) ROOF CLAY TILE. NOA 06-1213.03 SUBMITTED FOR THE |
| | MISSION CLAY TILE EXPIRED ON 05/20/09. NEED TO PROVIDE |
| | CURRENT NOA. |
| | |
| | B) ROOF TILE ADHESIVE. SEE CLAY TILE PRODUCT APPROVAL |
| | FOR LISTED ADHESIVES. |
| | |
| | C) FLAT ROOF NOA 07-0730.03. PROVIDE RAS 117 |
| | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER |
| | AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE |
| | OF NOA. |
| | C(1) SPECIFY WHICH APPROVED ASSEMBLY AND BASE SHEET |
| | FASTENING OPTION IS GOING TO BE USED FROM NOA |
| | SUBMITTED. |
| | |
| | 3- OWES $4117.68 WHICH IS THE BALANCE FOR THE PERMIT |
| | FEE. |
| | |
| | 4- SHEET A301. REVISE STUCCO SPECIFICATIONS ON SECTIONS |
| | THRU KITCHEN AND MASTER BATHROOM. TABLE R703.4 DOESN'T |
| | APPLY TO STUCCO. SEE TABLE R702.1(1) AND REVISE STUCCO |
| | THICKNESS AS REQUIRED. |
| | ALSO, SPECIFY TWO LAYERS OF WATER-RESISTANT BARRIER AS |
| | REQUIRED BY SEC. R703.6.3. |
| | |
| | 5- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR THE |
| | POLYCYNENE INSULATION TO BE USED TO VERIFY REQUIRED |
| | THICKNESS AND COORDINATE WITH THE ENERGY CALCULATIONS. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |