| Plan Review Notes For Permit 09120061 |
| Permit Number |
09120061 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-23 13:43:53 | ******DENIED***** | | | | | | | | | 1. THE SCOPE OF WORK IS PROJECTED IN SUITE 550 WHICH IS | | | ADJACENT TO SUITE 800. IS THIS THE 5TH FLOOR OR THE 8TH | | | FLOOR? PLEASE EXPLAIN. | | | | | | 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 3. AS OF 12/31/08, THE 2007 FLORIDA FIRE PREVENTION | | | CODE BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION | | | AND NFPA 1, UNIFORM FIRE CODE, 2006 EDITION SHALL BE | | | REFERENCED. | | | | | | 4. PLEASE DECLARE THE NEW OCCUPANCY TYPE/USAGE AND THE | | | OCCUPANT LOAD BASED ON THAT OCCUPANCY TYPE. | | | | | | 5. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFYING THE 75; TRAVEL | | | DISTANCE. | | | | | | 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS | | | AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|