| Plan Review Notes For Permit 09120046 |
| Permit Number |
09120046 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2010-01-27 08:27:21 | 1. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD, | | | DUCT, AND FIRE SUPPRESSION SYSTEMS. | | | | | | 2. THE EXISTING RATED SHAFT AND ORIGINAL GREASE DUCT | | | DISPLAYED ON SHEET 3.3.M IS TO BE FIELD VERIFIED AND | | | INSPECTED BY MECHANICAL INSPECTORS. ANY VIOLATIONS OF | | | CODE DISCOVERED WILL NEED TO BE CORRECTED BY SUBMITTING | | | PLANS AND PERMITS. | | | | | | 3. NO FIRE SPRINKLER PLANS PROVIDED. PLEASE SUPPLY | | | COMPLETE FIRE SPRINKLER PLANS ILLUSTRATING DESIGN, HEAD | | | LOCATION, WATER SUPPLY, FIRE DEPARTMENT CONNECTION, | | | VALVES AND ALL OTHER APPURTENANCES. SEPARATE SHOP | | | DRAWINGS WILL BE REQUIRED PRIOR TO ANY INSTALLATION. | | | | | | 4. ON PAGE 2.1E ONLY ONE HORN STROBE IS SHOWN IN THE | | | LOUNGE PROPER. ANOTHER ONE IS DISPLAYED IN THE MAIN | | | LOBBY OF THE BUILDING. ADDITIONAL HORN STROBES APPEAR | | | TO BE NEEDED. CONFLICTS EXIST BETWEEN THE FIRE ALARM | | | PLAN AND THE ELECTRICAL SHEETS. SEPARATE PLANS AND | | | PERMITS REQUIRED FOR THE FIRE ALARM SYSTEM SHALL BE UL | | | FOR CENTRAL STATION SERVICE. | | | | | | 5. ON THE FIRE ALARM PLANS IT INDICATES THAT THAT AN | | | ALARM, SUPERVISORY AND TROUBLE SIGNALS. A WATERFLOW | | | SIGNAL IS ALSO REQUIRED TO BE SENT. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|