| Date |
Text |
| 2010-02-03 07:59:01 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 09120046 |
| | ADD: 340 CLEMATIS ST |
| | CONT: GERARD CONTRACTING, INC. |
| | TEL: (561)281-5225 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | |
| | 1)THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S).PRODUCT APPROVALS |
| | SHALL BE SUBMITTED BEFORE ROUGH BUCK / FRAMING |
| | INSPECTION. |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | A) EXTERIOR GLAZED DOOR |
| | B) EXTERIOR BI-FOLD DOORS SOLAR INNOVATIONS |
| | C) FRENCH DOORS |
| | D) FIXED IMPACT WINDOWS |
| | E) PRE-MANUFACTURED A/C STANDS |
| | F) WALL LOUVER |
| | G) BAHAMA SHUTTERS |
| | |
| | 2) BUILDING APPROVED WITH EXCEPTION! THIS PLAN HAS BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL |
| | RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF |
| | RE-INSPECTION FEE(S). 106.3.3 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 3) BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). PLEASE PROVIDE |
| | MANUFACTURERS SPECS FOR WALK IN COOLER AND ACCORDANCE |
| | WITH 2603.4.1.3. |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |