| 2010-01-12 08:25:09 | BUILDING PLAN REVIEW |
| | PERMIT: 09120046 |
| | ADD: 340 CLEMATIS ST |
| | CONT: GERARD CONTRACTING, INC. |
| | TEL: (561)281-5225 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | JAN. 12/2009 |
| | |
| | 1) COMPLIED, UPDATE VALUE TO $220,000.00. |
| | |
| | 2) COMPLIED. |
| | |
| | 3) COVER SHEET INDICATES THIS BUILDING TO BE CONSIDERED |
| | A III-B SPRINKLERED BUILDING LEVEL IL ALTERATION. |
| | PLEASE SEE EXISTING BUILDING CODE (CHAPTER 9- CHANGE OF |
| | OCCUPANCY) AND SECTION 912. |
| | |
| | 3A) COMPLIED. |
| | |
| | 3B) COMPLIED. |
| | |
| | 3C) 2ND REQUEST, THE PLAN REVISION COVERSHEET INDICATES |
| | NOW THE SPACE TO BE FIRE SPRINKLERED, BUT NO FIRE |
| | SPRINKLER SCHEMATIC PLANS WERE SUBMITTED. 912.2 FL |
| | EXISTING BUILDING CODE. 912.2 FIRE PROTECTION SYSTEMS. |
| | FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE |
| | WITH SECTIONS 912.2.1 AND 912.2.2. |
| | |
| | 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A CHANGE IN |
| | OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES AN |
| | AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED ON |
| | THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE |
| | FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL BE |
| | PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. |
| | |
| | 2007 FBC- BUILDING, 903.2.1.2 GROUP A-2. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2 |
| | OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS |
| | EXISTS: |
| | (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE. |
| | |
| | 4-6) COMPLIED. |
| | |
| | 7) COMPLIED. |
| | 8) COMPLIED. |
| | |
| | 9) BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | 9A) EXTERIOR GLAZED DOOR |
| | 9B) EXTERIOR BI-FOLD DOORS SOLAR INNOVATIONS |
| | 9C) FRENCH DOORS NOTE# 6 |
| | 9D) FIXED IMPACT WINDOWS |
| | 9E) PRE-MANUFACTURED A/C STANDS |
| | 9F) WALL LOUVER |
| | 9G) BAHAMA SHUTTERS |
| | |
| | 10)BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | 2ND REQUEST. PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO |
| | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| | INFORMATION PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE |
| | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER |
| | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, |
| | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR |
| | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 11) BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 12) COMPLIED, NO BUCKS TO BE INSTALLED PER DESIGNER OF |
| | RECORD. |
| | |
| | 13) BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). |
| | PLEASE PROVIDE MANUFACTURERS SPECS FOR WALK IN COOLER |
| | AND ACCORDANCE WITH 2603.4.1.3. |
| | |
| | 14) COMPLIED. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |