| 2009-12-04 09:28:08 | |
| | ** DENIED** |
| | |
| | 1) NOTE: THE FOLLOWING CODES INDICATED ON THE SHEET ARE |
| | NOT ADOPTED BY THE STATE OF FLORIDA. |
| | PLANS LIST THE 2005 EDITION OF NFPA-70 ( NEC) HOWEVER |
| | THIS SHOULD BE 2008. THIS COULD HAVE BEEN REDLINED |
| | HOWEVER PLANS ARE COMING BACK FOR OTHER COMMENTS. |
| | |
| | ** SIDE NOTE** CODE SECTIONS REFLECTED ON PLANS ARE |
| | FROM THE 2004 FBC ON ELECTRICAL SHEETS.( ELECTRICAL |
| | NOTES) |
| | |
| | 2) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK |
| | IS REQUIRED TO INCLUDE VALUE FOR THE FOLLOWING; DESIGN |
| | COST, ALL LABOR, ALL EQUIPMENT, ALL MATERIALS/BUILDING |
| | MATERIALS FOR ALL TRADES WHETHER OR NOT ANY OF THESE |
| | ITEMS ARE OWNER SUPPLIED. VALUE APPLIED IS LOW. |
| | ** FBC 108.3 |
| | ** ONCE APPROPRIATE VALUE IS ASSESSED THEN ADDITIONAL |
| | FEES WILL BE REQUIRED BEFORE PERMIT ISSUANCE. |
| | |
| | 3) NOTE: RISER ONLY INDICATES ONE SET OF 3/0 AWG |
| | CONDUCTORS FOR FEEDERS AND SUB PANELS FOR 400AMPS. |
| | PLEASE SEE NEC 310.16 AS THESE ARE ONLY RATED FOR |
| | 200AMPS. HOWEVER THE SERVICE SIZE BEING PROVIDED IS |
| | 400AMPS. |
| | 240.4, 310.16 |
| | |
| | 4) NOTE: THIS IS A CHANGE IN OCCUPANCY UNDER THE |
| | EXISTING BUILDING CODE CHAPTER 9. PLEASE SEE 13-101.3 |
| | FOR CHANGES IN OCCUPANCY FOR ENERGY CODE COMPLIANCE. |
| | PLEASE SEE THE FOLLOWING ITEMS WHICH WERE NOT SHOWN ON |
| | PLANS FOR CODE COMPLIANCE OR OTHER ITEMS NOT SUBMITTED. |
| | MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE CHAPTER |
| | 13 HAS NOT BEEN MET. |
| | PLEASE SEE THE 2007 FBC W/2009 SUPPLEMENTS INCLUDING |
| | SECOND SET OF 2009 SUPPLEMENTS ADOPTED BY THE STATE ON |
| | OCTOBER 1ST, 2009. |
| | ALONG WITH THE SHOWN METHOD B ON PLANS, A FIXTURE |
| | LEGEND WITH SPECIFIC FIXTURES NEEDS TO BE SHOWN TO |
| | REVIEW FOR MINIMUM CODE COMPLIANCE. SHOWING A 2X4 |
| | FIXTURE WITH 2-32W BULBS DOES NOT GIVE THE ACTUAL |
| | ACCURATE WATTAGE/VA CONSUMPTION OF FIXTURE. PLEASE SEE |
| | 13-415.AB.5 FOR INTERIOR ALLOWANCES AND APPENDIX FOR |
| | FIGURING. |
| | |
| | 5) NOTE: PLEASE SUBMIT LIGHTING CONTROL INFORMATION, |
| | LEGEND, DETAILS TO MEET MINIMUM CODE COMPLIANCE FOR FBC |
| | 13-415.AB.1.1,.1.2 AND .1.3. |
| | THERE IS NO CONTROLS SHOWN ON PLANS FOR LIGHTING. |
| | PLANS HAVE SOME SORT OF INDICATION FOR A LIGHTING |
| | CONTROL PANEL AND THE RISER SHOWS A LIGHTING CONTROL |
| | PANEL. HOWEVER NO INFORMATION OR DETAILS ARE SHOWN??? |
| | PLANS DO NOT SHOW CONTROLS AS REQUIRED FOR THE OCCUPANT |
| | TO OVER RIDE ANY TIME OF DAY SCHEDULING. |
| | PLANS DO NOT SHOW CONTROLS IN LOCATIONS FOR THE |
| | OCCUPANT TO SEE *ALL* LIGHTING WHICH IS BEING |
| | OVERRIDDEN. |
| | PLANS NEED TO INDICATE ALL SEPARATE SPACE CONTROLS.( |
| | SHOWN IN OFFICE HOWEVER NOT OTHER AREAS) |
| | |
| | 6) NOTE: IF THERE IS GOING TO BE ANY OUTSIDE LIGHTING |
| | PLEASE SEE 13-415.AB.1.4 |
| | |
| | 7) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| | COORDINATE WITH PANEL SCHEDULES.408.4, 310.16, 240.4, |
| | 220, GIVEN AS GENERAL SECTIONS BASED ON THE FACT LOAD |
| | CALCULATIONS, CIRCUITING AND SIXE OF OVER CURRENT |
| | PROTECTION DEVICES CAN NOT BE VERIFIED FOR CODE |
| | COMPLIANCE IF THE PLANS AND PANEL SCHEDULE DO NOT |
| | COORDINATE. |
| | |
| | EXAMPLE: PLEASE SEE SIGN J-BOX OUT FRONT FOR EXAMPLE |
| | WHICH INDICATES CIRCUIT A41- YET THE PANEL SCHEDULE IS |
| | BLANK. SEE 600.5 FOR MINIMUM VA REQUIRED TO BE |
| | ADDITIONAL SIGN CIRCUIT. |
| | |
| | EXAMPLE: PLEASE SEE ANOTHER EXAMPLE IS TO CIRCUIT |
| | EMERGENCY AND EXIT LIGHTS PER 700.12F. ( ONLY SOME |
| | SHOWN, HOWEVER SEE COMMENT BELOW) |
| | |
| | EXAMPLE: PLEASE SEE B37 IN CLOSET AREA, WHICH BY PANEL |
| | SCHEDULE THIS IS LABELED. *BAG IN BOX*? |
| | |
| | EXAMPLE: PLEASE SEE B16 WHICH IS NOT ON PLANS. THIS |
| | LIGHTING IS ALSO NOT SHOWN FOR LIGHTING CONTROLS PER |
| | NOTE #5 ABOVE. |
| | |
| | EXAMPLE: PLEASE SEE LIGHTING PLAN WHICH INDICATES B19 |
| | ON PLAN AND PANEL SCHEDULE STATES BAR COOLER. HOW IS |
| | THIS ALSO A LIGHTING CIRCUIT? |
| | |
| | EXAMPLE: PLANS INDICATE CIRCUIT A-27 AT TWO COOLER DOOR |
| | LOCATIONS HOWEVER A-27/29 FEED THE EXHAUST HOOD. |
| | |
| | 8) NOTE: PLEASE COORDINATE PLANS. THE REFLECTED CEILING |
| | PLANS AND THE LIFE SAFETY PLAN DOES NOT MATCH WITH THE |
| | ELECTRICAL LIGHTING PLANS. MOST OF THE EMERGENCY AND |
| | EXIT LIGHTS ARE IN DIFFERENT LOCATIONS. |
| | SEE REAR EXIT AND OTHER AREA FIXTURES. SOME ARE SHOWN |
| | AS EXIT/EMERGENCY LIGHTS AND THEN THE ELECTRICAL PLANS |
| | ONLY INDICATE THE SAME FIXTURES AS EXIT. |
| | PLEASE SEE 700.12F. |
| | |
| | 9) NOTE: PLANS NEED TO COMPLETE BASE DESIGN FOR FIRE |
| | ALARM SYSTEM/DEVICES. ALL DEVICE LOCATIONS, HEIGHTS, |
| | LEVELS CANDELA AND DB RATINGS MUST BE SHOWN ON BASE |
| | PLANS FOR DESIGN INTENT. THE FIRE ALARM WILL BE |
| | REQUIRED UNDER SEPARATE PERMIT HOWEVER MINIMUM CODE |
| | COMPLIANCE DESIGN NEEDS TO BE SHOWN PER NFPA-72, FBC |
| | AND FS 633. SEE NEC 760 FOR CIRCUITING REQUIRED AS WELL |
| | AS NFPA 72 CHAPTER 4. |
| | ** THIS WILL NOT BE A PROVISO ITEM> |
| | |
| | 10) NOTE: ELECTRICAL PLANS ONLY INDICATE THE LOCATION |
| | OF TWO OF THE PANELS WHEREAS THE LIFE SAFETY SHEET AND |
| | OTHER SHEETS INDICATE ALL THREE PANELS. |
| | 110.26, 240.24 |
| | |
| | 11) NOTE: ALL LOW VOLTAGE SYSTEMS SUCH AS SOUND, CATV, |
| | PHONE ETC WILL BE UNDER SEPARATE PLANS AND PERMIT |
| | APPLICATION. THESE PLANS MAY NOT BE REFERENCED FOR ANY |
| | OF THESE ITEMS AS PLANS DO NOT SHOW COMPLETED SYSTEMS |
| | AT THIS TIME. |
| | ** NO SYMBOL LEGEND ON PLANS FOR ANY DEVICE WHICH MAY |
| | BE INCLUDED. |
| | |
| | 12) NOTE: DETAIL FOR ELECTRICAL SYSTEMS UNDER HOOD AND |
| | PERTAINING TO HOOD FOR SHUT DOWN WILL ALSO BE REQUIRED |
| | UNDER SEPARATE PERMIT AND PLANS. ( NONE SHOWN AND HOOD |
| | IS UNDER SEPARATE PERMIT). |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |