| 2009-12-07 18:24:00 | BUILDING PLAN REVIEW |
| | PERMIT: 09120046 |
| | ADD: 340 CLEMATIS ST |
| | CONT: GERARD CONTRACTING, INC. |
| | TEL: (561)281-5225 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DEC. 07/2009 |
| | |
| | 1) LOW EVALUATION PLEASE REVIEW WORK TO BE COMPLETED |
| | UNDER THIS PERMIT AND CONSTRUCTION VALUE. W P B |
| | ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| | BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, AND |
| | PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| | FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 2) CHANGE OF OCCUPANCY: BEFORE A PERMIT TO CONSTRUCT, |
| | MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH |
| | COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED |
| | BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED |
| | TO THE PERMIT APPLICATION. PLEASE CALL (561)233-5025 |
| | FOR MORE INFORMATION. |
| | |
| | 3) COVER SHEET INDICATES THIS BUILDING TO BE CONSIDERED |
| | A III-B UNSPRINKLERED BUILDING LEVEL ???LL ALTERATION. |
| | PLEASE SEE EXISTING BUILDING CODE (CHAPTER 9- CHANGE OF |
| | OCCUPANCY) AND SECTION 912. |
| | |
| | 3A) PLANS DO NOT INDICATE WHERE THE 2HR OCCUPANCY WALL |
| | WILL BE PLACED SEPARATING THE TENANCY FROM THE COMMON |
| | AREAS AND THE 2ND FLOOR BUSINESS OCCUPANCIES. 2009 FBC |
| | ??? BUILDING. 803.9.1.2 FIRE-RESISTANCE-RATED |
| | CONSTRUCTION. ACOUSTICAL CEILING SYSTEMS THAT ARE PART |
| | OF FIRE-RESISTANCE-RATED CONSTRUCTION SHALL BE |
| | INSTALLED IN THE SAME MANNER USED IN THE ASSEMBLY |
| | TESTED AND SHALL COMPLY WITH THE PROVISIONS OF CHAPTER |
| | 7. |
| | 912.5.3 EXISTING BUILDING CODE. |
| | |
| | 3B) SHEET 1.0A DOOR# 4 DOES NOT INDICATE WHAT TYPE OF |
| | ROOM IS LOCATED BEHIND THIS DOOR. THIS MAY BE AN ISSUE |
| | DEPENDING ON (1) WHERE THE TENANT SEPARATION WALL IS |
| | LOCATED, AND THE USAGE OF THE ROOM. EXAMPLE IF THIS IS |
| | A ELEVATOR EQUIPMENT ROOM, 3006.1 ACCESS. AN APPROVED |
| | MEANS OF ACCESS SHALL BE PROVIDED TO ELEVATOR MACHINE |
| | ROOMS AND OVERHEAD MACHINERY SPACES. ELEVATOR MACHINE |
| | ROOMS CAN NOT BE LOCATED WITHIN A TENANT SPACE. |
| | |
| | 3C) 912.2 FL EXISTING BUILDING CODE. 912.2 FIRE |
| | PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTIONS 912.2.1 AND |
| | 912.2.2. |
| | |
| | 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A CHANGE IN |
| | OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES AN |
| | AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED ON |
| | THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE |
| | FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL BE |
| | PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. |
| | |
| | 2007 FBC- BUILDING, 903.2.1.2 GROUP A-2. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2 |
| | OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS |
| | EXISTS: |
| | (2). THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE. |
| | |
| | 4) 2007 EXIST BLDG CODE.912.3 INTERIOR FINISH. IN AREAS |
| | OF THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY |
| | CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY |
| | CLASSIFICATION. |
| | COVER SHEET THE MINIMUM INTERIOR FINISH SCHEDULE TABLE |
| | 803.5 PLEASE REVIEW ROOMS AND ENCLOSED SPACES FOR |
| | UNSPRINKLED BUILDING, A2 OCCUPANCY SCHEDULE WILL NEED |
| | TO BE REVISED FOR SPRINKLED BUILDINGS. |
| | |
| | 5) SHEET 1.0A DOOR# 11 APPEARS TO BE AN EXIT DOOR |
| | LEADING TO THE EXTERIOR, THE DOOR IS LABELED AS A |
| | SERVICE DOOR. THE LIFE SAFETY PLANS INDICATE NO EXIT |
| | SIGN AT THIS DOOR BUT TAKES YOU DOWN A CORRIDOR AND |
| | THROUGH 2 OTHER DOORS BEFORE ENTERING THE EXIT TO THE |
| | EXTERIOR. WITHIN THE CORRIDOR THERE IS A ROOM AND DOOR |
| | THAT ARE NOT IDENTIFIED PLEASE PROVIDE ADDITIONAL |
| | INFORMATION. DOORS MARKED AS # 3 IN THIS CORRIDOR DO |
| | NOT HAVE A FIRE RATING IN THE DOOR SCHEDULE. TABLE |
| | 715.4. DOOR # 11 SWINGS THE WRONG DIRECTION FBC- |
| | BUILDING 1008.1.2. |
| | |
| | 6) SHEET 1.0A DOOR# 5 ALSO IS NOT IDENTIFIED AS A FIRE |
| | RATED DOOR IN THE DOOR SCHEDULE, TENANT SEPARATION WALL |
| | AND OCCUPANCY SEPARATION WALL. TABLE 715.4. |
| | |
| | 7) SHEET 1.0A NOTE# 5 INDICATES THE USE OF BI-FOLD |
| | GLASS DOORS, NONE OF THE FLOOR PLANS INDICATE IF THE |
| | DOORS ARE TO SWING IN OR OUT, IF THEY SWING OUT PLEASE |
| | PROVIDE WHERE THE PROPERTY LINE IS LOCATED IN REGARDS |
| | TO THE BI-FOLD DOOR LOCATION. |
| | 2007 FBC- BUILDING 3202.2 ENCROACHMENTS ABOVE GRADE AND |
| | BELOW 8 FEET IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC |
| | RIGHT-OF-WAY ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN |
| | HEIGHT SHALL BE PROHIBITED EXCEPT AS PROVIDED FOR IN |
| | SECTIONS 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS |
| | SHALL NOT OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. |
| | |
| | 8) SHEET 1.0A ALSO INDICATES THE USE OF BAHAMA |
| | SHUTTERS, THE SAME CONCERNS ABOUT ENCROACHMENT INTO THE |
| | RIGHT AWAY WITH REGARDS TO THE HEIGHT OF THE SHUTTERS. |
| | 3202.2 FBC-BUILDING. |
| | |
| | 9) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES, |
| | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING |
| | REPORTS, MISSING REPORTS ARE AS FOLLOWS: |
| | 9A) EXTERIOR GLAZED DOOR |
| | 9B) EXTERIOR BI-FOLD DOORS SOLAR INNOVATIONS |
| | 9C) FRENCH DOORS NOTE# 6 |
| | 9D) FIXED IMPACT WINDOWS |
| | 9E) PRE-MANUFACTURED A/C STANDS |
| | 9F) WALL LOUVER |
| | 9G) BAHAMA SHUTTERS |
| | |
| | 10) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 12) PLANS DO NOT INDICATE IF THERE IS TO BE USE OF WOOD |
| | BUCKS OR NOT. NORMALLY THE PRODUCT APPROVALS DO NOT |
| | INCLUDE THE ATTACHMENT OF WOOD BUCKS. COMPONENTS AND |
| | CLADDING |
| | |
| | 13) PLEASE PROVIDE MANUFACTURERS SPECS FOR WALK IN |
| | COOLER AND ACCORDANCE WITH 2603.4.1.3. |
| | |
| | 14) PLEASE PROVIDE COMPLIANCE WITH 11-5.1- 11-4. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |