| Plan Review Notes For Permit 09120037 |
| Permit Number |
09120037 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-02 13:13:08 | REROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- THIS BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". | | | SEC. 1609.4 FBC WITH 2009 REVISIONS. ENGINEER TO REVISE | | | RAS 117 CALCULATIONS AND TAS 105 CALCULATIONS AS | | | REQUIRED. | | | ***NOTE: ENGINEER TO PROVIDE HIS NAME AND LICENSE # ON | | | THE SIGNED SHEETS AS REQUIRED BY CHAPTER 471 FLORIDA | | | STATUTES. | | | | | | 2- ENGINEER TAS 105 REPORT IS MISSING THE INFORMATION | | | REGARDING THE SPECIFIC COMPONENT TO BE SECURED. NO | | | COMPONENT WAS MARKED. | | | | | | 3- ENGINEER TAS REPORT IS REFERENCING THE 2001 FBC. SEE | | | TAS-105 STATISTICAL ANALYSIS PAGE AND UPDATE AS | | | REQUIRED. | | | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | 5- ANY ROOF EQUIPMENT REQUIRES SEPARATE PERMIT FOR | | | RE-INSTALLATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|