| Plan Review Notes For Permit 09120028 |
| Permit Number |
09120028 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-05-18 15:37:56 | *****PROVISO***** | | | | | | READY FOR PERMIT ISSUANCE; PLAN SHEET FA-1 STAMPED, | | | INITIALED, AND DATED WITH THE FOLLOWING ATTACHED | | | PROVISO. | | | | | | PRIOR TO THE FIRE ALARM FINAL (302), REVISED PLAN SHALL | | | BE REQUIRED WITH THE FOLLOWING INFORMATION: | | | | | | 1. FIRE ALARM PLAN DEPICTING THE LAYOUT OF ROOMS FOR | | | THIS NEW DAY CARE OCCUPANCY. | | | 2. PROVIDE INFORMATION ON THE HEAT DETECTOR DEVICE AND | | | HOW IT RELATES TO THE FIRE ALARM SYSTEM, AND SHOWN IN | | | THE FIRE ALARM RISER. | | | 3. THE CORRECT ADDRESS SHALL BE IN THE TITLE BLOCK OF | | | EACH SUBMITTED PLAN SHEET. IT SHOULD BE 724 BUNKER | | | ROAD, NOT 724 N. BUNKER ROAD. | | | 4. RELOCATE THE FIRE ALARM CONTROL PANEL (FACP) FROM | | | THE KITCHEN. REASONING: A SMOKE DETECTOR IS REQUIRED | | | ABOVE THE FACP, BUT WITH THE SMOKE DETECTOR BEING IN | | | THE KITCHEN, IT IS SUSCEPTIBLE TO FIRE ALARM ACTIVATION | | | FROM SMOKE CAUSED BY NORMAL COOKING OPERATIONS (WHICH | | | CAN BECOME A NUISANCE TO THE OCCUPANTS, NEIGHBORS, AND | | | FIRE EMERGENCY RESPONSE UNITS) . | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|