| 2009-12-22 16:01:33 | DENIED |
| | REFERENCE: |
| | FBC-2007 FUEL GAS |
| | FBC-2007 CHAPTER 1 |
| | FLORIDA ADMINSITRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | A. PLANS SUBMITTED INDICATE "COPIES FOR REFERENCE |
| | ONLY". SHT P-4 GAS ISOMETRIC HAS BEEN SUBMITTED NOT FOR |
| | REFERENCE BUT FOR PERMIT. IF THE DESIGN PROFESSIONAL IS |
| | AN ENGINEER LEGALLY REGISTERED UNDER THE LAWS OF THIS |
| | STATE REGULATING THE PRACTICE OF ENGINEERING AS |
| | PROVIDED FOR IN CHAPTER 471, FLORIDA STATUTES THEN HE |
| | OR SHE SHALL AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE |
| | AND DATE TO SAIN DRAWINGS. SECTION 106.1. THE SHEETS |
| | SUBMITTED HAVE A TITLE BLOCK OF THE ENGINEER OF RECORD. |
| | EITHER THE ENGINEER OF RECORD SHALL SIGN, SEAL & DATE |
| | THE SHEETS SUBMITTED FOR PERMIT OR A NEW ENGINEER SHALL |
| | SUBMIT THE REQUIRED GAS RISER DIAGRAM AND SIGN, SEAL |
| | AND DATE SUCH PLANS. |
| | |
| | B. THE FOLLOWING INFORMATION IS REQUIRED FOR A GAS |
| | PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR |
| | 2007 FUEL GAS CODE. -- THE ISOMETRIC SHALL SHOW ALL |
| | PIPING TO THE METER IN ORDER TO DETERMINE THE REQUIRED |
| | PIPE SIZE. |
| | |
| | 2. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 6. SHT P-4 GAS RISER DIAGRAM SHOWS 47,000 BTU ADDED FOR |
| | THE OVEN, BUT MANUF. SHEETS SUBMITTED INDICATE THE BTU |
| | LOAD TO BE 66,000. PLEASE CLARIFY. |
| | |
| | C. THE VALUATION OF THE PROJECT APPEARS TO BE LOW. SEE |
| | BELOW FOR VALUATION REQUIREMENTS. |
| | |
| | 104.6.5 BUILDING PERMIT VALUATION. IF |
| | IN THE OPINION OF THE BUILDING OFFICIAL |
| | THE CLAIMED VALUATION OF BUILDING, AL- |
| | TERATION, STRUCTURE, ELECTRICAL, GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES |
| | AND/OR BONA FIDED SIGNED CONTRACTS (EX- |
| | CLUDING LAND VALUE) TO MEET THE APPROVAL |
| | OF THE BUILDING OFFICIAL. FOR PERMITTING |
| | PURPOSES, VALUATION FOR BUILDINGS AND |
| | SYSTEMS SHALL BE FOUND IN MARSHALL AND |
| | SWIFT OR THE SOUTHERN BUILDING CODE |
| | CONGRESS INTERNATIONAL VALUATION TABLES, |
| | LATEST EDITION, AND SHALL BE BASED ON |
| | TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRIC, PLUMBING, MECHAN- |
| | ICAL, INTERIOR FINISH, NORMAL SITE WORK |
| | (EXCAVATION AND BACKFILL FOR BUILDINGS), |
| | ARCHITECTURAL AND DESIGN FEES, OVERHEAD |
| | AND PROFIT, EXCLUDING ONLY LAND VALUE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |