| Plan Review Notes For Permit 09110596 |
| Permit Number |
09110596 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-01 07:36:44 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. HISTORIC APPROVAL REQUIRES PANELS IN FRONT. SUBMIT A | | | PRODUCT APPROVAL, REVISED FLOOR PLAN, REVISED | | | INSTALLATION SCHEDULE FOR PANELS FOR FRONT ELEVATION. | | | | | | 2. APPLICATION PROJECT DETAIL STATES "REAR PORCH, | | | REPAIR HANDICAP RAMP, REPAIR VINYL SIDING, DRYWALL | | | REPAIRS." SCOPE OF REPAIRS WAS NOT INDICATED IN THE | | | PLANS SUBMITTED. ON A FLOOR PLAN, PLEASE INDICATE | | | APPROXIMATE LOCATION AND SCOPE (APPROX SQUARE FOOT | | | AREA) OF REPAIR AREAS. SUBJECT TO INSPECTOR'S | | | DISCRETION, A DETAIL MAY BE REQUIRED. | | | | | | |
|