Plan Review Notes
Plan Review Notes For Permit 09110567
Permit Number 09110567
Review Stop E
Sequence Number 2
Notes
Date Text
2009-12-08 13:40:04 
 ** DENIED **
  
 1) NOTE: THE APPLIED VALUE FOR THE COMPLETE SCOPE OF IS
 VERY LOW. THE VALUE SHALL INCLUDE, ALL DESIGN COSTS,
 ALL EQUIPMENT, MATERIALS, LABOR ETC EVEN IF ANY OF
 THESE ITEMS ARE OWNER SUPPLIED.
 FBC 108.3 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 2) NOTE: PLANS SUBMITTED NEED TO STATE RELEVANT CODES
 IN WHICH DESIGN IS DONE. ALL PERMIT APPLICATIONS
 SUBMITTED OCTOBER
 1ST, 2009 OR LATER ARE UNDER THE 2008 NEC.
 ** THERE IS A SUBSTANTIAL AMOUNT OF CHANGES IN THE 2008
 NEC UNDER 690.
  
 3) NOTE: PLANS SUBMITTED ARE REQUIRED TO CONTAIN THE
 DESIGNER OF RECORD INDICATED. PLEASE SEE FS 471.003
 WHEN MEETING EXCEPTIONS FOR REQUIRED DESIGN
 PROFESSIONAL. IF MEETING EXCEPTION, DESIGN IS STILL
 REQUIRED TO BE DONE BY A LICENSED PROFESSIONAL PER FS
 489.
 PLEASE BE SURE TO PRINT AND SIGN ON SHEETS. PLEASE CALL
 IF THERE ARE QUESTIONS.
  
 4) NOTE: PLEASE SEE 310.15(A) AND (B) FOR DE-RATING FOR
 THE NUMBER OF CONDUCTORS AND THE DE-RATING FOR THE
 AMBIENT AIR EXPOSED TO DIRECT SUB LIGHT. PLEASE SEE
 310.15(B)(2)(C).
 PLEASE ALSO SEE 690.7 AND PROVIDE CALCULATIONS FOR
 BOTH.
  
 5) NOTE: PLEASE PROVIDE DOCUMENTATION FROM FLORIDA
 POWER AND LIGHT SO THEY ARE AWARE OF SYSTEM BEING
 CONNECTED INTO THE GRID. PLEASE CHECK WITH LOCAL
 SERVICE REP AND SEE FPL2009 SERVICE STANDARDS.
 ELECTRICAL RISER INDICATES A *BI-DIRECTIONAL METER*
 HOWEVER THE BASE BUILDING PLANS DO NOT INDICATE THIS.
 PLEASE COORDINATE ALL ONCE REVISED.
  
 6) NOTE: PLEASE SEE 690.5 FOR GROUND FAULT, PLEASE
 INDICATE ON PLANS.
  
 7) NOTE: DISCONNECTING MEANS FOR SERVICING EQUIPMENT ON
 ROOF.
  
 8) NOTE: PLEASE PROVIDE LISTING ON ALL EQUIPMENT. SOME
 OF THE PRODUCT DATA SHEETS INDICATE LISTING FROM A NRTL
 HOWEVER NOT ALL.
 PLEASE SEE 690.4D, 110.3, 90.7 ETC
 PLEASE ALSO SEE OSHA FOR COMPLETE LISTING OF NATIONALLY
 RECOGNIZED TESTING LABORATORIES.
  
 9) NOTE: PLEASE HAVE THE REVIEW STAMP AND SIGNATURE
 FROM THE RESPONSIBLE BASE BUILDING DESIGNER ON PLANS.
 PLEASE BE SURE IT IS THE ENGINEER OF RECORD ALONG WITH
 ORIGINAL SIGNATURE AND SHOP DRAWING REVIEW STAMP.
 PLEASE DO NOT STAMP ON THE BACK OF A BLANK SHEET.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved