| Plan Review Notes For Permit 09110556 |
| Permit Number |
09110556 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-10 15:50:46 | | | | ** DENIED ** | | | | | | | | | ** SOME OF THE ITEMS BELOW COULD HAVE BEEN REDLINED | | | HOWEVER NOT ALL. | | | | | | 1) NOTE: PLEASE SEE FLORIDA STATUTES 471.025, FAC | | | 61G15-23.002 AS PLANS ARE REQUIRED TO BE SIGNED, DATED | | | AND SEALED BY THE DESIGN PROFESSIONAL. | | | | | | 2) NOTE: PLEASE SEE R313.2.1. PLEASE SHOW LOCATIONS OF | | | ALL EXISTING OR NEW SMOKE ALARMS MEETING CURRENT | | | NFPA-72 11.5.1, 11.8.3 REQUIREMENTS. IF THE EXISTING | | | SMOKE ALARMS DO NOT MEET CURRENT CODES, NEW SMOKE | | | ALARMS WILL BE REQUIRED. PLAY ROOM VICINITY REQUIRED TO | | | CONTAIN SMOKE ALARM. | | | PLEASE SHOW ON PLANS. | | | | | | 3) NOTE: PLEASE INDICATE NEW RECEPTACLES PER 406.11, | | | 2008 NEC. | | | | | | 4) NOTE: PLEASE SEE INDICATE NEW RECEPTACLES PER 210.12 | | | OF THE 2008 NEC. | | | | | | 5) NOTE: PLEASE INDICATE THE DESIGN CODE RELEVANT. 2008 | | | NFPA-70. PLANS INDICATE 2005. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|