2009-12-30 19:09:05 
  
  
 PASSED/PROVISO:
  
 REVISION REQUIRED:
  
 SHT P-2 GAS RISER DIAGRAM. PER TABLE 402.4(2) 1-1/2
 INCH PIPE IS REQUIRED UP TO THE STOVE, (TOTAL 589,000
 BTU'S), AND 1-1/4 INCH PIPE IS REQUIRED UP TO THE
 CHARBROILER, (TOTAL 320,000 BTU'S). ALL SHUT OFF VALVES
 SHALL ALSO BE SIZED ALSO PER TABLE 402.4(2). THE SOV
 FOR THE STOVE SHALL BE 1 INCH, AND THE FRYERS SHALL BE
 3/4". ALL OTHERS SHALL BE MINIMUM 1/2 INCH.
  
 THE MANUF. SPECIFICATION SHEETS FOR THE SALAMANDER
 INDICATE TOTAL BTU'S AT 66,000, BUT THE ISOMETRIC RISER
 DIAGRAM INDICATE 30,000. PLEASE CLARIFY, EITHER CHANGE
 THE RISER DIAGRAM OR SUBMIT MANUF. SPECIFICATION SHEETS
 TO REFLECT THE BTU LOAD INDICATED ON THE RISER DIAGRAM.
  
  
  
 .