| 2009-12-29 16:10:53 | ** PROVISO ** |
| | |
| | **REVISION REQUIRED |
| | |
| | ***IMPORTANT** A PROVISO IS BEING GIVEN FOR SOME |
| | CIRCUITING AND PANEL SCHEDULES. |
| | |
| | |
| | 1) NOTE: PLEASE SEE CIRCUITING ON PLANS FOR ALL |
| | EMERGENCY LIGHTS. THESE MUST BE WIRED TO LOCAL LIGHTING |
| | BRANCH CIRCUIT PER 700.12F OR MEET EXCEPTION. SOME |
| | AREAS ON PLANS SUCH AS BACK HALLWAY, BATHROOMS WOULD |
| | NOT MEET EXCEPTIONS SO THEY MUST BE CIRCUITED TO LOCAL |
| | LIGHTING BRANCH CIRCUIT. |
| | |
| | 2) NOTE: ALL OCCUPANCY SENSORS CONTROLLING LIGHTS IN |
| | MULTI-GANG BATHROOMS SHALL BE * FAIL SAFE ON* TYPE |
| | DEVICES. NFPA-101 7.8.1.2.2, FBC 1016.1.2 |
| | |
| | 3) NOTE: WALK IN COOLER DOES NOT INDICATE ANY LIGHTS? |
| | THIS IS NOT REQUIRED FOR THIS REVIEWER HOWEVER IF THERE |
| | IS GOING TO BE LIGHTING THEN CONTROLS NEED TO BE SHOWN. |
| | AREA OFF OF KITCHEN IDENTIFIED AS LIQUOR STORAGE ON A |
| | SHEETS DOES NOT HAVE AUTOMATED LIGHTING CONTROLS IN |
| | SPACE AS REQUIRED PER FBC 13-415.AB.1.2. |
| | |
| | 4) NOTE: ALL 15/20AMP 120V RECEPTACLE LOCATIONS IN |
| | KITCHEN AREA ARE REQUIRED TO BE GFI OR GFI PROTECTED. |
| | CIRCUITS FOR EVEN DEDICATE EQUIPMENT IS REQUIRED TO |
| | HAVE PROTECTION. |
| | PLEASE SEE 2008 NEC 210.8B2 |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |