Plan Review Notes
Plan Review Notes For Permit 09110494
Permit Number 09110494
Review Stop E
Sequence Number 2
Notes
Date Text
2009-12-29 16:10:53** PROVISO **
  
 **REVISION REQUIRED
  
 ***IMPORTANT** A PROVISO IS BEING GIVEN FOR SOME
 CIRCUITING AND PANEL SCHEDULES.
  
  
 1) NOTE: PLEASE SEE CIRCUITING ON PLANS FOR ALL
 EMERGENCY LIGHTS. THESE MUST BE WIRED TO LOCAL LIGHTING
 BRANCH CIRCUIT PER 700.12F OR MEET EXCEPTION. SOME
 AREAS ON PLANS SUCH AS BACK HALLWAY, BATHROOMS WOULD
 NOT MEET EXCEPTIONS SO THEY MUST BE CIRCUITED TO LOCAL
 LIGHTING BRANCH CIRCUIT.
  
 2) NOTE: ALL OCCUPANCY SENSORS CONTROLLING LIGHTS IN
 MULTI-GANG BATHROOMS SHALL BE * FAIL SAFE ON* TYPE
 DEVICES. NFPA-101 7.8.1.2.2, FBC 1016.1.2
  
 3) NOTE: WALK IN COOLER DOES NOT INDICATE ANY LIGHTS?
 THIS IS NOT REQUIRED FOR THIS REVIEWER HOWEVER IF THERE
 IS GOING TO BE LIGHTING THEN CONTROLS NEED TO BE SHOWN.
 AREA OFF OF KITCHEN IDENTIFIED AS LIQUOR STORAGE ON A
 SHEETS DOES NOT HAVE AUTOMATED LIGHTING CONTROLS IN
 SPACE AS REQUIRED PER FBC 13-415.AB.1.2.
  
 4) NOTE: ALL 15/20AMP 120V RECEPTACLE LOCATIONS IN
 KITCHEN AREA ARE REQUIRED TO BE GFI OR GFI PROTECTED.
 CIRCUITS FOR EVEN DEDICATE EQUIPMENT IS REQUIRED TO
 HAVE PROTECTION.
 PLEASE SEE 2008 NEC 210.8B2
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  