| Date |
Text |
| 2009-12-02 16:43:40 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | CITY WPB CODE OF ORDINANCES |
| | |
| | 1. SHT P-1 THE GREASE INTERCEPTOR SHALL BE APPROVED. |
| | PLEASE SUBMIT THE MANUF. SPECIFICATION & INSTALLATION |
| | SHEETS. SECTION 1003.2. |
| | |
| | 2. SHT P-1 THE GREASE INTERCEPTOR SHALL NOT BE LOCATED |
| | IN THE FOOD PREP AREA. ARTICLE III SECTION |
| | 90-124(7)(B). |
| | |
| | 3. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED |
| | ACCORDING TO TABLE 1003.5.1. THE FOLLOWING INFORMATION |
| | IS REQUIRED: |
| | A. NUMBER OF SEATS IN THE DINING AREA. |
| | B. GALLONS OF WASTE PER SEAT. (25 OR 10) SEE TABLE. |
| | C. NUMBER OF HOURS RESTAURANT IS OPEN. |
| | D. LOADING FACTOR (.75). |
| | |
| | 4. SHTS P-1 & P-2 WASTE THAT DO NOT REQUIRE TREATMENT |
| | OR SEPARATION SHALL NOT BE DISCHARGED INTO ANY |
| | INTERCEPTOR OR SEPARATOR. SECTIONS 1003.2 & 1003.3.1. |
| | REMOVE THE ICE MAKER AND THE CONDENSATE FROM THE |
| | WALK-IN COOLER AND CONNECT TO THE SANITARY SYSTEM. |
| | |
| | 5. SHT P-1 SHOWS 4 WATER FALL FIXTURES. PLEASE INDICATE |
| | IF THERE WILL BE WATER SUPPLY LINE CONNECTING TO THE |
| | FIXTURES. IF SO BACKFLOW PREVENTION IS REQUIRED PER |
| | SECTION 608.2. PLEASE CLARIFY HOW THE WATER FALL |
| | FIXTURE WILL BE FILLED WITH WATER. |
| | |
| | 6. SHT P-2 H & C WATER RISER DIAGRAM SHOWS WHAT APPEARS |
| | TO BE AIR CHAMBERS AT EACH FIXTURE. AIR CHAMBERS ARE |
| | NOT APPROVED. PLEASE DELETE FROM RISER DIAGRAM. PDI-WH |
| | 201. WATER HAMMER ARRESTORS ARE REQUIRED AND THE DISH |
| | WASHER AND ICE MAKER PER SECTION 604.9 PLEASE SHOW THE |
| | REQUIRED WATER HAMMER ARRESTORS. |
| | |
| | 7.SHT P-2 THE GREASE SYSTEM IS NOT VENTED. SECTION |
| | 901.2. PLEASE SHOW THE VENT FOR THE SYSTEM. SECTION |
| | 912.2. |
| | |
| | 8. SHT P-2 SANITARY RISER DIAGRAM. THE BRANCH LINE FOR |
| | THE WATER CLOSET & SUSHI BAR IS NOT VENTED AS WELL AS |
| | THE BRANCH LINE TO THE EXPRESSO MACHINE/3 COMPARTMENT |
| | SINK. SECTION 901.2. PLEASE SHOW VENTS. |
| | |
| | 9. SUBMIT THE FLOW RATE FOR THE FLOOR DRAIN, THE 3 |
| | COMPARTMENT SINK AND THE MOP SINK. SECTION 1003.3.4.2. |
| | |
| | 10. SHT P-2 SHOWS NO SUPPLY OR DRAINAGE FOR THE |
| | DISHWASHER. PLEASE CLARIFY. SECTIONS 601.1 & 701.1. |
| | PLEASE CLARIFY. |
| | |
| | 11. SHTS P-1 & P-2 BARS #1 & #2 SHOWS NO DRAINAGE FROM |
| | THE ICE WELLS. PLEASE CLARIFY. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |