Plan Review Notes
Plan Review Notes For Permit 09110494
Permit Number 09110494
Review Stop P
Sequence Number 1
Notes
Date Text
2009-12-02 16:43:40DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 CITY WPB CODE OF ORDINANCES
  
 1. SHT P-1 THE GREASE INTERCEPTOR SHALL BE APPROVED.
 PLEASE SUBMIT THE MANUF. SPECIFICATION & INSTALLATION
 SHEETS. SECTION 1003.2.
  
 2. SHT P-1 THE GREASE INTERCEPTOR SHALL NOT BE LOCATED
 IN THE FOOD PREP AREA. ARTICLE III SECTION
 90-124(7)(B).
  
 3. SHT P-1 THE GREASE INTERCEPTOR SHALL BE SIZED
 ACCORDING TO TABLE 1003.5.1. THE FOLLOWING INFORMATION
 IS REQUIRED:
 A. NUMBER OF SEATS IN THE DINING AREA.
 B. GALLONS OF WASTE PER SEAT. (25 OR 10) SEE TABLE.
 C. NUMBER OF HOURS RESTAURANT IS OPEN.
 D. LOADING FACTOR (.75).
  
 4. SHTS P-1 & P-2 WASTE THAT DO NOT REQUIRE TREATMENT
 OR SEPARATION SHALL NOT BE DISCHARGED INTO ANY
 INTERCEPTOR OR SEPARATOR. SECTIONS 1003.2 & 1003.3.1.
 REMOVE THE ICE MAKER AND THE CONDENSATE FROM THE
 WALK-IN COOLER AND CONNECT TO THE SANITARY SYSTEM.
  
 5. SHT P-1 SHOWS 4 WATER FALL FIXTURES. PLEASE INDICATE
 IF THERE WILL BE WATER SUPPLY LINE CONNECTING TO THE
 FIXTURES. IF SO BACKFLOW PREVENTION IS REQUIRED PER
 SECTION 608.2. PLEASE CLARIFY HOW THE WATER FALL
 FIXTURE WILL BE FILLED WITH WATER.
  
 6. SHT P-2 H & C WATER RISER DIAGRAM SHOWS WHAT APPEARS
 TO BE AIR CHAMBERS AT EACH FIXTURE. AIR CHAMBERS ARE
 NOT APPROVED. PLEASE DELETE FROM RISER DIAGRAM. PDI-WH
 201. WATER HAMMER ARRESTORS ARE REQUIRED AND THE DISH
 WASHER AND ICE MAKER PER SECTION 604.9 PLEASE SHOW THE
 REQUIRED WATER HAMMER ARRESTORS.
  
 7.SHT P-2 THE GREASE SYSTEM IS NOT VENTED. SECTION
 901.2. PLEASE SHOW THE VENT FOR THE SYSTEM. SECTION
 912.2.
  
 8. SHT P-2 SANITARY RISER DIAGRAM. THE BRANCH LINE FOR
 THE WATER CLOSET & SUSHI BAR IS NOT VENTED AS WELL AS
 THE BRANCH LINE TO THE EXPRESSO MACHINE/3 COMPARTMENT
 SINK. SECTION 901.2. PLEASE SHOW VENTS.
  
 9. SUBMIT THE FLOW RATE FOR THE FLOOR DRAIN, THE 3
 COMPARTMENT SINK AND THE MOP SINK. SECTION 1003.3.4.2.
  
 10. SHT P-2 SHOWS NO SUPPLY OR DRAINAGE FOR THE
 DISHWASHER. PLEASE CLARIFY. SECTIONS 601.1 & 701.1.
 PLEASE CLARIFY.
  
 11. SHTS P-1 & P-2 BARS #1 & #2 SHOWS NO DRAINAGE FROM
 THE ICE WELLS. PLEASE CLARIFY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved