2009-12-09 17:06:05REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-1 SHOWS FRESH AIR INTAKES LOCATED DIRECTLY
 ADJACENT TO THE ALLEY IN THE BACK OF THE BUILDING.
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS
 VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS,
 PARKING LOTS AND LOADING DOCKS IN ACCORDANCE WITH FBC-M
 401.4.1.
  
 2. PAGE M-1 SHOWS A DETAIL FOR A TANKLESS WATER HEATER
 AND VENT. THE LOCATION OF THE "TERMIATOR VENT" IS NOT
 SHOWN ON THE PLANS. ALSO, THE DETAIL SHOWS THE VENT
 TERMINATING IN A LOUVER. PROVIDE MANUFACTURER'S
 INSTRUCTIONS SHOWING THIS AS AN ACCEPTABLE MEANS OF
 VENT TERMINATION IN ACCORDANCE WITH FBC-FG 304.1.
 NOTE: WH VENT CAN NOT PASS THROUGH A PLENUM PER FBC-M
 601.5.
  
 3. PLANS FOR KITCHEN HOOD AND WALK-IN COOLERS SHALL BE
 SUBMITTED SEPARATELY WITH SEPARATE PERMIT APPLICATIONS.
 NOTE: THE SHAFT FOR THE KITCHEN EXHAUST DUCT MUST BE
 INDEPENDENT AND USED FOR NO PURPOSE OTHER THAN THE
 KITCHEN EXHAUST GREASE DUCT PER FBC-M 506.3.10.
  