| Plan Review Notes For Permit 09110494 |
| Permit Number |
09110494 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-09 17:06:05 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-1 SHOWS FRESH AIR INTAKES LOCATED DIRECTLY | | | ADJACENT TO THE ALLEY IN THE BACK OF THE BUILDING. | | | MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS | | | SHALL BE LOCATED A MINIMUM OF 10 FEET HORIZONTALLY FROM | | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT SOURCE, SUCH AS | | | VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, | | | PARKING LOTS AND LOADING DOCKS IN ACCORDANCE WITH FBC-M | | | 401.4.1. | | | | | | 2. PAGE M-1 SHOWS A DETAIL FOR A TANKLESS WATER HEATER | | | AND VENT. THE LOCATION OF THE "TERMIATOR VENT" IS NOT | | | SHOWN ON THE PLANS. ALSO, THE DETAIL SHOWS THE VENT | | | TERMINATING IN A LOUVER. PROVIDE MANUFACTURER'S | | | INSTRUCTIONS SHOWING THIS AS AN ACCEPTABLE MEANS OF | | | VENT TERMINATION IN ACCORDANCE WITH FBC-FG 304.1. | | | NOTE: WH VENT CAN NOT PASS THROUGH A PLENUM PER FBC-M | | | 601.5. | | | | | | 3. PLANS FOR KITCHEN HOOD AND WALK-IN COOLERS SHALL BE | | | SUBMITTED SEPARATELY WITH SEPARATE PERMIT APPLICATIONS. | | | NOTE: THE SHAFT FOR THE KITCHEN EXHAUST DUCT MUST BE | | | INDEPENDENT AND USED FOR NO PURPOSE OTHER THAN THE | | | KITCHEN EXHAUST GREASE DUCT PER FBC-M 506.3.10. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|