| Plan Review Notes For Permit 09110494 |
| Permit Number |
09110494 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-12-03 16:03:12 | *****DENIED***** | | | | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. ON SHEET A-1UNDER FIRE PREVENTION CODE COMPLIANCE, | | | IT IS INCORRECTLY STATED FLORIDA FIRE PREVENTION CODE | | | 2006 EDITION W/ BROWARD COUNTY AMENDMENTS. | | | | | | 3. CORRECT VERBAGE ON SHEET A-5 SHOULD READ LIFE (NOT | | | LIVE) SAFETY PLAN. CORRECT VERBAGE ON COVER SHEET ALSO. | | | | | | 4. PROVIDE INFORMATION ON THE FABRICS/MATERIALS AS IT | | | RELATES TO FLAME PROPAGATION PERFORMANCE CRITERIA. | | | | | | 5. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE | | | PROJECT SITE LOCATION. | | | | | | 6. DOES THE COVERED PATIO HAVE FIRE SPRINKLER | | | PROTECTION? | | | | | | 7. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE | | | PROJECT SITE LOCATION. | | | | | | | | | CAPT. MICHALE A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|