Plan Review Notes
Plan Review Notes For Permit 09110494
Permit Number 09110494
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-12-03 16:03:12*****DENIED*****
  
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A-1UNDER FIRE PREVENTION CODE COMPLIANCE,
 IT IS INCORRECTLY STATED FLORIDA FIRE PREVENTION CODE
 2006 EDITION W/ BROWARD COUNTY AMENDMENTS.
  
 3. CORRECT VERBAGE ON SHEET A-5 SHOULD READ LIFE (NOT
 LIVE) SAFETY PLAN. CORRECT VERBAGE ON COVER SHEET ALSO.
  
 4. PROVIDE INFORMATION ON THE FABRICS/MATERIALS AS IT
 RELATES TO FLAME PROPAGATION PERFORMANCE CRITERIA.
  
 5. PROVIDE A LAYOUT OF THE FIRE SPRINKLER HEADS FOR THE
 PROJECT SITE LOCATION.
  
 6. DOES THE COVERED PATIO HAVE FIRE SPRINKLER
 PROTECTION?
  
 7. PROVIDE A LAYOUT OF THE FIRE ALARM DEVICES FOR THE
 PROJECT SITE LOCATION.
  
  
 CAPT. MICHALE A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722