2009-12-02 18:17:41 
 ** DENIED**
  
  
 1) NOTE: PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING
 MINIMUM CODES FOR ALL APPLICATIONS MADE AFTER OCTOBER
 1ST, 2009
 PLANS HAVE LOCATIONS IN WHICH STATE THE 2004 FPC WHICH
 SHOULD BE 2007 W/2009 SUPPLEMENTS.
 PLANS CONTAIN NOTES FOR BOTH THE 2006 AND 2003
 NFPA-101.
 NOTE ON PLANS FOR BROWARD COUNTY?
 **PLEASE ADJUST CODES AS FOLLOWS FOR THIS REVIEWER AS
 APPLICABLE. SOME OTHER CODES MAY BE NOTED BY OTHER
 TRADES.
  
 THE 2008 NFPA-70 WAS ADOPTED ON OCTOBER 1ST,2009.
 PLEASE ADJUST DESIGNS FOR NEW REVISED CODES.
 2006 NFPA-101: ADOPTED 12/31/08 BY FAC 69A-60.004
 2002 NFPA-72: ADOPTED 12/31/08 FAC 69A-3.012
 2006 NFPA-1: ADOPTED 12/31/08 FAC 69A-60.003( TO BE
 NOTED BY FIRE REVIEW
 2007 FLORIDA FIRE PREVENTION CODE. ( TO BE NOTED BY
 FIRE REVIEW) PLANS STATE 2006 FFPC.
  
  
 2) NOTE: THIS IS A CHANGE IN OCCUPANCY UNDER THE
 EXISTING BUILDING CODE CHAPTER 9. PLEASE SEE 13-101.3
 FOR CHANGES IN OCCUPANCY FOR ENERGY CODE COMPLIANCE.
 PLEASE SEE THE FOLLOWING ITEMS WHICH WERE NOT SHOWN ON
 PLANS FOR CODE COMPLIANCE OR OTHER ITEMS NOT SUBMITTED.
 MINIMUM COMPLIANCE WITH FLORIDA BUILDING CODE CHAPTER
 13 HAS NOT BEEN MET.
 PLEASE SEE THE 2007 FBC W/2009 SUPPLEMENTS INCLUDING
 SECOND SET OF 2009 SUPPLEMENTS ADOPTED BY THE STATE ON
 OCTOBER 1ST, 2009.
  
 2A) NOTE: PLEASE SUBMIT COMPLETE LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW OCCUPANCY. PLEASE SEE THE
 FOLLOWING SECTIONS AND CALL TO GO OVER ANY OF THESE
 SECTIONS.
 IN A MEETING HELD BEFORE PLANS WERE SUBMITTED THIS
 INFORMATION WAS GIVEN TO ARCHITECT PRESENT HOWEVER NO
 LIGHTING PERFORMANCE CALCULATIONS WERE SUBMITTED OR
 COMPLIANCE SHOWN ON PLANS.
 PLEASE SEE 13-101.1.3, 13-101.4.1, 13-400.0.B,
 13-400.0.B.4, 13-400.2.
  
 2B) NOTE: PLEASE SEE 13-415.AB.5 FOR INTERIOR LIGHTING
 PERFORMANCE CALCULATIONS REQUIRED. PLEASE KEEP IN MIND
 IF USING A FORM FROM THE FLORIDA BUILDING CODE FOR
 SPACE BY SPACE, THEN ONE FORM IS REQUIRED FOR EACH
 SPACE. IF USING FLA-COM THEN PLEASE BE SURE TO COMPLETE
 THE INPUT DATA REPORT WHICH IS PART OF THE FLA COM
 PROGRAM.
  
 ** IT IS TO BE NOTED THAT A FIXTURE SCHEDULE FOR ALL
 NEW UPGRADE FIXTURE IS REQUIRED IN ORDER TO REVIEW FOR
 LIGHTING ALLOWANCES.
 ** IT IS ALSO TO BE NOTED TO SEE APPENDIX SECTION FOR
 FIGURING TRACK LIGHTING.
  
 2C) NOTE: PLEASE SEE 13-415.AB.2 FOR EXTERIOR LIGHTING
 ALLOWANCES. ( SEE COMMENTS BELOW FOR CONTROLS)
  
 3) NOTE: PLEASE SUBMIT AND SHOW MINIMUM COMPLIANCE WITH
 FBC 13-415.AB.1.1,.1.2,.1.3 AND .1.4 FOR ALL LIGHTING
 CONTROLS.
 PLANS ARE NOT COMPLETE AT THIS TIME WITH LIGHTING
 CONTROLS FOR MAIN DINING AREAS INSIDE AND OUTSIDE.
 NO SWITCH LEGS, WIRING DIAGRAMS, OR METHOD OF CONTROLS
 ARE SHOWN FOR MOST AREAS.
 KITCHEN AREAS ARE NOT COMPLIANT AS ONLY STANDARD
 SWITCHES ARE SHOWN FOR COMPLIANCE.
 AUTOMATED LIGHTING CONTROLS FOR ALL LIGHTING IS
 REQUIRED.
 PLEASE SEE 13-415.AB.1.1 AND .1.2 FOR SPACE AND
 SEPARATE SPACES.
 PLEASE SEE 13-415.AB.1.3 FOR ADDITIONAL CONTROLS
 REQUIRED FOR ACCENT LIGHTING AND OTHER LIGHTING AS
 LISTED IN THE FBC.
 SEE NOTE #5 BELOW FOR NEW EXTERIOR LIGHTING CONTROLS
 REQUIRED.
 ** THIS WAS ALSO GONE OVER IN MEETING HELD BEFORE PLANS
 WERE SUBMITTED. IT WAS STATED THAT A WHOLE NEW SYSTEM
 WAS GOING TO BE INSTALLED YET THE PLANS DO NOT SHOWN
 ANY FOR MINIMUM CODE. THE DETAIL ON E-3 DOES NOT
 PROVIDE INFORMATION FOR AUTOMATED SHUT OFFS/OVER-RIDES,
 ZONES,
 ALL PRESENT SEEMED TO BE AWARE OF LIGHTING CONTROL
 REQUIREMENTS AND THEY WERE GOING TO BE INSTALLED. IF
 THERE ARE FURTHER QUESTIONS, IT IS RECOMMENDED DESIGNER
 CALL TO GO OVER.
  
 4) NOTE: PLANS INDICATE MANY FIXTURES AS EXISTING
 HOWEVER NO CONTROLS/SWITCH LEGS AS NOTED ABOVE ARE
 SHOWN. SOME OF THESE LOCATIONS SUCH AS ABOVE THE SIDE
 WALK AREA ARE ALL NOTED AS EXISTING HOWEVER THEY ARE
 NOT CURRENTLY LOCATED ON SITE AND HAVE NOT BEEN FOR A
 LONG TIME. THESE WOULD BE NEW.
 PLEASE COMPLETE PLANS WITH ALL SWITCHING, SWITCH LEGS
 FOR CONTROLS FOR MINIMUM CODE COMPLIANCE AS NOTED ABOVE
 FOR CURRENT CODE.
 PLEASE BE SURE TO SEE FBC 1016.1.2 AND NFPA-101
 7.8.1.2.2 FOR ANY OCCUPANCY SENSORS CONTROLLING ANY
 NORMAL OR EMERGENCY EGRESS LIGHTING.
  
 5) NOTE: PLEASE SEE SECTION 13-415.AB.1.4 FOR EXTERIOR
 LIGHTING. THE CODE ALLOWS TWO METHODS OF CONTROLS.
 PLEASE INDICATE WHICH ONE WILL BE DONE. THIS INCLUDE
 NEW OUTSIDE DINING AREA.
 CODE PERMITS ASTRONOMICAL TIME CLOCK WITH MINIMUM OF
 10HR PROGRAMMING BACK UP OR PHOTO-SENSOR CONTROLS. IF
 THE EXISTING TIME CLOCK CONTAINS THIS PLEASE SHOW ON
 THE DETAIL ON E3.
  
 6) NOTE: THERE ARE SOME AREAS ON PLANS WHICH ELECTRICAL
 INFORMATION IS NOT COMPLETED. AN EXAMPLE OF THIS IS THE
 SUSHI BAR WHICH INDICATES A NEW WATER FEATURE AND
 COOLER HOWEVER NO ELECTRICAL, OR CIRCUITING. IT IS NOT
 POSSIBLE TO REVIEW FOR CODE COMPLIANCE IF INFORMATION
 IS NOT PRESENT.
 THERE IS NO EQUIPMENT LEGEND ON PLANS.
 PLEASE SEE 210.8B2 FOR ALL 15A/20AMP RECEPTACLES IN
 KITCHEN AREAS WHICH ARE REQUIRED TO BE GFI/GFI
 PROTECTED. THIS IS WHETHER OR NOT THEY FEED COUNTER
 SPACE/TOP RECEPTACLES. PLEASE ALSO SEE BAR AREAS AND
 AREAS WHERE RECEPTACLES ARE LOCATED WITHIN SINK AREAS.
  
 7) NOTE: PLEASE SEE 2008 NEC 406.8 A AND B FOR WEATHER
 RESISTANT TYPE RECEPTACLES REQUIRED.
  
  
 8) NOTE: PLEASE SEE 220.43 (A)AND (B) FOR SHOW WINDOW
 CALCULATIONS AND TRACK LIGHTING LOAD CALCULATIONS TO BE
 SHOWN. ALL LIGHTING LOADS ARE FIGURED TOGETHER HOWEVER
 SECTION GIVEN REQUIRES ADDITIONAL LOADS.
 SHOW WINDOWS AND TRACK LIGHTING CAN NOT BE CONSIDERED
 AS GENERAL LIGHTING. PLEASE SHOW.
  
 9) NOTE: THE EXISTING RISER IS NOT CLEAR AND CONFUSING.
 HOW IS THERE TWO CT CANS SHOWN FOR ONE TENANT? THERE
 ARE TWO SHOWN AS Z GALLERIE HOWEVER THIS DOES NOT SEEM
 POSSIBLE.
 THE OTHER PART IS THE OTHER CT ALSO LABELED FOR Z
 GALLERIE IS SHOWN NOT FEEDING ANYTHING???
 PLEASE REVISE SERVICE AND RE-LABEL PER 230.2E, 215.5
 ETC.
  
 10) NOTE: PLEASE SHOW ALL FIRE ALARM AND HORN, STROBE
 OR HORN STROBE DEVICES MEETING MINIMUM CODE FOR ADA.
 PLANS SHOW SOME DEVICES HOWEVER NO LEVELS, HEIGHTS,
 MINIMUM CANDELA LEVELS OR DB LEVELS INDICATED.
 AS NOTED ABOVE THIS IS A CHANGE IN OCCUPANCY TO A
 HIGHER HAZARD PER THE FBC AND ANY DEVICES NOT CURRENTLY
 MEETING CURRENT CODES WILL BE REQUIRED TO BE UPDATED.
 PLEASE SEE FBC 11-4.28.1.,2 AND .3. IF THERE ARE
 QUESTIONS PLEASE CALL.
 EVEN THOUGH FIRE ALARM PERMIT AND PLANS WILL BE
 SEPARATE FS 633 REQUIRES ALL BASE BUILDING PLANS TO
 SHOW MINIMUM CODE COMPLIANCE DESIGN INTENT.
  
 11) NOTE: PLEASE SEE 408.4 IN THE NEC. THE PANEL
 SCHEDULE WILL BE REQUIRED TO BE UPDATED WITH ALL
 CIRCUITS. PLANS WILL ALSO BE REQUIRED TO HAVE ALL
 CIRCUITS LABELED AND COORDINATED WITH PANEL SCHEDULES.
 THE USE OR WORDING OF *LIGHTING* OR *RECEPTACLES* IS
 NOT ACCEPTABLE. THE FOLLOWING IS EXTRACTED DIRECTLY
 FROM THE NEC HANDBOOK.
 **
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.**
  
 ** AS THIS IS AN EXISTING SITUATION A PROVISO CAN BE
 SET UP TO SUBMIT COMPLETE REVISED PANEL SCHEDULES AND
 CIRCUITING ON PLANS FOR ALL EXISTING AND NEW BEFORE
 FINAL.
 ALL NEW IS REQUIRED TO BE COORDINATED AT THIS TIME FOR
 ALL NEW RECEPTACLES, LIGHTING AND EQUIPMENT.
 ALL REVIEW OF LOADING ON CIRCUITS WILL BE DONE ONCE
 PLANS HAVE BEEN REVISED AND COORDINATED WITH PANEL
 SCHEDULES.
  
 12) NOTE: PLEASE INDICATE CIRCUITING FOR ALL EMERGENCY
 LIGHTING AND EXIT LIGHTS PER 700.12F. ( LOCAL LIGHTING
 BRANCH CIRCUIT). THIS CAN BE DONE AS A NOTE ON PLANS AS
 MANY OF THESE ITEMS ARE EXISTING.
 NEW LOCATIONS NEED TO BE CIRCUITED AND SHOWN AT THIS
 TIME.
  
  
 13) NOTE: PLEASE SUBMIT PHOTO-METRIC LEVELS FOR EGRESS
 PATHS. THERE ARE LOCATIONS SUCH AS BOTH BATHROOMS WHICH
 DO NOT APPEAR TO MEET MINIMUM FOOT CANDLES REQUIRED BY
 THE LIFE SAFETY CODE.
 PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.1.2, .2.2 FOR
 MINIMUM LEVELS UNDER EMERGENCY AND NORMAL CONDITIONS.
  
 14) NOTE: THE APPLIED VALUE FOR COMPLETE SCOPE OF WORK
 IS REQUIRED TO INCLUDE VALUE FOR THE FOLLOWING; DESIGN
 COST, ALL LABOR, ALL EQUIPMENT, ALL MATERIALS/BUILDING
 MATERIALS FOR ALL TRADES WHETHER OR NOT ANY OF THESE
 ITEMS ARE OWNER SUPPLIED. VALUE APPLIED IS LOW.
 ** FBC 108.3
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  