Plan Review Notes
Plan Review Notes For Permit 09110494
Permit Number 09110494
Review Stop B
Sequence Number 1
Notes
Date Text
2009-12-02 13:28:27BUILDING PLAN REVIEW
 PERMIT: 09110494
 ADD: 314 CLEMATIS ST
 CONT: LARREA AGUIRRE CONSTRUCTION, LLC
 TEL: (954)993-7301
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 DECEMBER 02/ 2009
 ACTION: DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 2) SHEET A1:
 2A) PLEASE UPDATE CODE COMPLIANCE NOTES, THE CURRENT
 FIRE PREVENTION CODE THAT IS REFRENCED IN THE FBC
 CHAPTER 35IS THE 2007 NOT THE 2006 PLEASE UPDATE THE
 PLANS.
  
 2B) PLEASE DELETE THE BROWARD COUNTY AMENDMENTS, THIS
 IS A STATE WIDE CODE. ONLY CHAPTER 1 THE ADMINISTRATIVE
 CODE IS A LOCAL ADAPTION, WEST PALM BEACH AMENDMENTS.
  
 2C) OCCUPANT LOAD CALCULATION, REFRENECE SECTION 1004.2
 OF THE FBC. WHERE REQUIRED BY THE BUILDING OFFICIAL, AN
 APPROVED AISLE, SEATING OR FIXED EQUIPMENT DIAGRAM
 SUBSTANTIATING ANY INCREASE IN OCCUPANT LOAD SHALL BE
 SUBMITTED. WHERE REQUIRED BY THE BUILDING OFFICIAL,
 SUCH DIAGRAM SHALL BE POSTED. PLEASE INDICATE THE
 SEATING AND AISLE WIDTHS ON THE LIFE SAFETY PLAN.
  
 2D) SHEET A1 ALSO INDICATES WINDOW AND EXTERIOR DOOR
 PRESSURES, BUT THE PLANS FAILS TO PROVIDE THE WIND
 DESIGN CRITERIA THE PRESSURES WERE DERIVED FROM:
 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 3) SHEET A2:
 3A) PLEASE INDICATE COMPLIANCE WITH ACCESSIBILITY
 REQUIREMENT:
 11-4.32.2 SEATING. IF SEATING SPACES FOR PEOPLE IN
 WHEELCHAIRS ARE PROVIDED AT FIXED TABLES OR COUNTERS,
 CLEAR FLOOR SPACE COMPLYING WITH SECTION 11-4.2.4 SHALL
 BE PROVIDED. SUCH CLEAR FLOOR SPACE SHALL NOT OVERLAP
 KNEE SPACE BY MORE THAN 19 INCHES (485 MM) (SEE FIGURE
 45).
  
 ALL FIXED SEATING IN PUBLIC FOOD SERVICE
 ESTABLISHMENTS, IN ESTABLISHMENTS LICENSED UNDER THE
 BEVERAGE LAW FOR CONSUMPTION ON THE PREMISES, AND IN
 ALL OTHER FACILITIES GOVERNED BY REFERENCE SECTION
 11-4.1 SHALL BE DESIGNED AND CONSTRUCTED IN ACCORDANCE
 WITH THE FOLLOWING REQUIREMENTS:
  
 (1) ALL AISLES ADJACENT TO FIXED SEATING SHALL PROVIDE
 CLEAR FLOOR SPACE FOR WHEELCHAIRS.
  
 (2) WHERE THERE ARE OPEN POSITIONS ALONG BOTH SIDES OF
 SUCH AISLES, THE AISLES SHALL BE NOT LESS THAN 52
 INCHES (1321 MM) WIDE.
  
 3B) PLEASE INDICATE COMPLIANCE WITH ACCESSIBILITY
 REQUIREMENT: 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR
 MODIFIED IN THIS SECTION, RESTAURANTS AND CAFETERIAS
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 11-4.1 TO
 SECTION 11-4.35. WHERE FIXED TABLES (OR DINING COUNTERS
 WHERE FOOD IS CONSUMED BUT THERE IS NO SERVICE) ARE
 PROVIDED, AT LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF
 THE FIXED TABLES (OR A PORTION OF THE DINING COUNTER)
 SHALL BE ACCESSIBLE AND SHALL COMPLY WITH SECTION
 11-4.32 AS REQUIRED IN SECTION 11-4.1.3(18). IN
 ESTABLISHMENTS WHERE SEPARATE AREAS ARE DESIGNATED FOR
 SMOKING AND NONSMOKING PATRONS, THE REQUIRED NUMBER OF
 ACCESSIBLE FIXED TABLES (OR COUNTERS) SHALL BE
 PROPORTIONALLY DISTRIBUTED BETWEEN THE SMOKING AND
 NONSMOKING AREAS. IN NEW CONSTRUCTION, AND WHERE
 PRACTICABLE IN ALTERATIONS, ACCESSIBLE FIXED TABLES (OR
 COUNTERS) SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR
 FACILITY.
  
 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS SERVED
 AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN HEIGHT FOR
 CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING
 AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS
 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE PROVIDED
 IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE
 AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 3C) PLEASE PROVIDE INFORMATION HOW THE VENTILATION
 SHAFT WILL BE TRANSFORMED INTO A MECHANICAL SHAFT AND
 LEAVE THE ELEVATOR CAR AND ELECTRICAL CONDUITS &
 EQUIPMENT ASSOCIATED WITH THTE ELEVATOR. HOW WILL THE
 ELEVATOR OPENING ON THE 2ND FLOOR BE HANDLED? PLEASE
 REVIEW COMMENTS FROM FIRE AND MECHANICAL AS TO THE
 REMOVAL OF EQUIPMENET NOT AASOCIATED WITH EXHAUST AIR.
 707.8 PENETRATIONS. PENETRATIONS IN A SHAFT ENCLOSURE
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTION 712 AS
 REQUIRED FOR FIRE BARRIERS.
  
 707.8.1 PROHIBITED PENETRATIONS. PENETRATIONS OTHER
 THAN THOSE NECESSARY FOR THE PURPOSE OF THE SHAFT SHALL
 NOT BE PERMITTED IN SHAFT ENCLOSURES.
  
 4) SHEET A-4 COVERED PATIO CEILING, THERE SEEMS TO BE A
 DISCREPANCY IN THE SYSTEMS BEING USED TO FINISH THE
 CEILING. THE PLANS INDICATE THE USE OF A PAREX EFIS
 CEILING SYSTEM, WITH WIRE LATH AND A DENSGLASS
 SHEATHING BOARD.
  
 4A) PLEASE PROVIDE PRODUCT APPROVAL FOR THE PAREX EFIS
 SYSTEM.
  
 4B) PLEASE PROVIDE PRODUCT APPROVAL FOR THE DENSGLASS
 SHEATHING BOARD.
  
 4C) WIRE LATH, THE PLANS CALL FOR THE WIRE LATH TO BE
 LAYERED BETWEEN THE DENSGLASS AND PAREX EFIS SYSTEM.
 PLEASE PROVIDE THE GAUGE OF WIRE AND TYPE OF WIRE LATH.
 PLANS INDICATE THE STANDARD ASTM C-1063 BUT THE
 DESIGNER NEEDS TO INDICATE THE TYPE OF MATERIAL. ALSO
 HOW THE WIRE LATH IS TO BE ATTACHED TO THE DENSGLASS
 AND NOT DIRECTLY TO THE METAL HI-HAT?
  
 INFORMATIONAL 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 5) SHEET A5:
  
 5A) GENERAL NOTE# 2 PLEASE UPDATE NOTE TO THE CURRENT
 2007FBC W/ 2009 SUPPLEMENTS.
  
 5B) LOCATED AT THE PATIO FRONT ENTRY THERE (2) RAMPS
 ARE INDICATED. ADDITIONAL INFORMATION IS REQUIRED. THE
 PLANS INDICATE THE RISE TO BE 5 ????? TALL BUT THE RUN
 HAS NOT BEEN PROVIDED. THIS INFORMATION IS REQUIRED TO
 SE IF THE REQUIREMENTS OF 11-4.8.5 ARE REQUIRED.
  
 5C) DJ BOOTH- NO INFORMATION WAS PROVIDED IN THE
 ARCHITECTURAL PLANS ON THE HAND RAILS BUT S5 INDICATES
 THE USE OF ONLY (1) HANDRAIL. PLEASE REVIEW SECTION
 1009.10, 1012.5 & 11-4.9.4(2) HORIZONTAL EXTENSIONS.
  
 6) SHEET A-6 BOTH THE MEN???S AND LADIES RESTROOM ENTRY
 DOORS. THE PLANS INDICATE A 1???-0??? MANEUVERING
 CLEARANCE AT THE LATCH SIDE OF THE DOOR. PLEASE REVIEW
 11-4.13.6 AND FIGURE 25(A) WHICH REQUIRES A MINIMUM OF
 18??? AND A PREFERRED 24???.
  
 7) PRODUCT APPROVALS. FLORIDA ADMINISTRATIVE CODE RULE
 9B-72
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
  
 7A) EXTERIOR GLAZED FRONT ENTRY DOORS- NOT PART OF THE
 STOREFRONT NOA
 7B) WALL LOUVERS
 7C) STORM SHUTTERS / PANELS
 7D) EFIS SYSTEMS
 7E) DENSGLASS
 7F) A/C PRE-MANUFACTURED ROOF STANDS
  
 7G) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7H) 106.3.3 PRODUCT APPROVALS .THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7I) 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION
 QUESTION# 13 RECOGNIZING SUCH CONCERNS AS ABSENTEE
 OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE
 SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST BE
 SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR
 REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE OFFICIAL NOTIFICATION
 BY THE NATIONAL WEATHER SERVICES OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 7J) STORM SHUTTERS & OR PANELS. PLEASE CIRCLE THE
 CONNECTION TYPE (HEADER / SILL) WITH THAT OF THE
 PRODUCT APPROVAL, TYPE OF ANCHOR TO BE INSTALLED AND
 SPACING FOR THE ASSOCIATED PRESSURES. FL BLD CODE 2004
 SECTION 106.3.3, 1609.1.4, 1714.5.1 & EXIST BUILD CODE
 507.3. PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING OPENING SIZES, STORY
 HEIGHTS, UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT
 STORM
 BAR REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 7K) 1511.7 ROOF MOUNTED MECHANICAL UNIT S SHALL BE
 MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE
 ROOF SURFACE, OR WHERE ROOFING MATERIALS EXTEND BENEATH
 THE UNIT, ON RAISED EQUIPMENT SUPPORTS PROVIDING A
 MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH TABLE
 1511.7.
  
 7L) MECH. 301.13 WIND RESISTANCE MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 ON THE EQUIPMENT & THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FL BLDG CODE. THIS MAY BE
 ACCOMPLISHED BY DESIGN OR BY APPLICATION OF SECTION
 301.13.1.
  
 THIS WIND REQUIREMENT IS FOR THE ACTUAL ATTACHMENT OF
 THE EQUIPMENT TO THE STRUCTURE BELOW AS WELL AS THE
 EQUIPMENT ITSELF, (A/C ROOF TOP CONDENSERS, EXHAUST
 FANS).
  
 8) THE PLANS ARE DEFICIENT IN THE WALL & CEILING
 FINISHES. SHEET A1 DOES PROVIDE THE PARAMETERS FOR THE
 MATERIALS FOR FLAME SPREAD &SMOKE DEVELOPMENT BUT NOT
 THE ACTUAL FINISH MATERIALS. OUR CONCERNS ARE:
  
 8A) 803.4.1 DIRECT ATTACHMENT AND FURRED CONSTRUCTION.
  
 8B) 803.4.2 SET-OUT CONSTRUCTION.
  
 8C) 803.4.4 MATERIALS.
  
 8D) 803.6 TEXTILES.
  
 8E) 803.9.1 MATERIALS AND INSTALLATION. ACOUSTICAL
 MATERIALS COMPLYING WITH THE INTERIOR FINISH
 REQUIREMENTS OF SECTION 803 SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND
 APPLICABLE PROVISIONS FOR APPLYING INTERIOR FINISH.
  
 8F) 803.9.1.1 SUSPENDED ACOUSTICAL CEILINGS. SUSPENDED
 ACOUSTICAL CEILING SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE PROVISIONS OF ASTM C 635 AND ASTM C
 636.
 PROVIDE DOCUMENTATION, INFORMATIONAL 106.1.1* W.P.B.
 ADMINISTRATIVE CODE/2004 DRAWINGS & SPECIFICATIONS
 SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE
 QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL
 CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE
 TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN
 PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS
 A SUBSTITUTE FOR SPECIFIC INFORMATION". CONSTRUCTION
 DOCUMENTS SHALL BE SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 8G) 806.3 FOAM PLASTIC. FOAM PLASTIC USED AS TRIM IN
 ANY OCCUPANCY SHALL COMPLY WITH SECTION 2604.2.
  
 8H) 806.4 PYROXYLIN PLASTIC. IMITATION LEATHER OR OTHER
 MATERIAL CONSISTING OF OR COATED WITH A PYROXYLIN OR
 SIMILARLY HAZARDOUS BASE SHALL NOT BE USED IN GROUP A
 OCCUPANCIES.
  
 8I) 806.5 INTERIOR TRIM. MATERIAL, OTHER THAN FOAM
 PLASTIC USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD AND SMOKE-DEVELOPED INDEX WHEN
 TESTED IN ACCORDANCE WITH ASTM E 84, AS DESCRIBED IN
 SECTION 803.1. COMBUSTIBLE TRIM, EXCLUDING HANDRAILS
 AND GUARDRAILS, SHALL NOT EXCEED 10 PERCENT OF THE
 AGGREGATE WALL OR CEILING AREA IN WHICH IT IS LOCATED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved