Plan Review Notes
Plan Review Notes For Permit 09110408
Permit Number 09110408
Review Stop E
Sequence Number 1
Notes
Date Text
2009-12-09 16:25:43 
 ** DENIED **
  
 ** REVIEW UNDER 2008 NEC.
  
 1) NOTE: PLEASE KNOW THE FOLLOWING CODES WHICH ARE
 RELEVANT TO THE DESIGN SHOULD BE ON PLANS.
  
 2008 NFPA-70 (PLANS DO NOT INDICATE ANY SPECIFIC
 EDITION ON COVER SHEET)
  
 3) NOTE: PLEASE SEE ELECTRICAL PLANS. THERE ARE
 KEYNOTES #1 THROUGH #7, YET ELECTRICAL PLANS ARE
 MISSING THE ACTUAL NOTATIONS FOR #1, #5
  
 4) NOTE: PLEASE INDICATE WHETHER OR NOT THERE EXISTING
 OR NEW DISCONNECTS PER 514.11. THIS CAN BE DONE WITH A
 NOTE AS LONG AS LOCATION MEETS CODE.
  
 ** IF ALL OTHER TRADE REVIEWS PASS, THIS MAY BE
 REQUESTED TO BE DONE AS A PROVISO WHICH WOULD REQUIRE
 PLANS TO BE REVISED AND SUBMITTED BEFORE INSPECTIONS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  