| Notes |
| Date |
Text |
| 2009-12-09 16:25:43 | | | | ** DENIED ** | | | | | | ** REVIEW UNDER 2008 NEC. | | | | | | 1) NOTE: PLEASE KNOW THE FOLLOWING CODES WHICH ARE | | | RELEVANT TO THE DESIGN SHOULD BE ON PLANS. | | | | | | 2008 NFPA-70 (PLANS DO NOT INDICATE ANY SPECIFIC | | | EDITION ON COVER SHEET) | | | | | | 3) NOTE: PLEASE SEE ELECTRICAL PLANS. THERE ARE | | | KEYNOTES #1 THROUGH #7, YET ELECTRICAL PLANS ARE | | | MISSING THE ACTUAL NOTATIONS FOR #1, #5 | | | | | | 4) NOTE: PLEASE INDICATE WHETHER OR NOT THERE EXISTING | | | OR NEW DISCONNECTS PER 514.11. THIS CAN BE DONE WITH A | | | NOTE AS LONG AS LOCATION MEETS CODE. | | | | | | ** IF ALL OTHER TRADE REVIEWS PASS, THIS MAY BE | | | REQUESTED TO BE DONE AS A PROVISO WHICH WOULD REQUIRE | | | PLANS TO BE REVISED AND SUBMITTED BEFORE INSPECTIONS. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|