Plan Review Notes
Plan Review Notes For Permit 09110374
Permit Number 09110374
Review Stop P
Sequence Number 1
Notes
Date Text
2009-12-07 09:58:04DENIED
 REFERENCE:
 FBC-2007 PLUMBING
  
 1. SHT 1 SANITARY ISOMETRIC. RISER DIAGRAM. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. AND ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT. SECTION 909.1. PLEASE SUBMIT AN ISOMETRIC
 SHOWING THE CORRECT CONNECTION FROM THE SERVICE SINK
 AND DRINKING FOUNTAIN TO THE BUILDING DRAIN.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  