Plan Review Notes
Plan Review Notes For Permit 09110374
Permit Number 09110374
Review Stop E
Sequence Number 1
Notes
Date Text
2009-11-30 13:23:32 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1 SEE.13-415.AB.2 EXTERIOR LIGHTING.
 SHOW COMPLIANCE ON THE PLAN. THIS CAN BE DEMONSTRATED
 ON THE PLANS INDICATING THE WATTAGES OF THE LUMINAIRES
 CHOSEN FOR THE PROJECT CONFORM TO THE DENSITY
 REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE SCHEDULE
 TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 2} THE 2008 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 1 OCTOBER 2009. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS
 CHANGE.
  
 3} THE GROUNDING ELECTRODE CONDUCTOR MUST BE A MINIMUM
 OF 1/0 PER 250.66
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  