| 2009-11-30 13:23:32 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING |
| | |
| | 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE |
| | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A |
| | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD |
| | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR |
| | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING |
| | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN |
| | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| | POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION13-415.B.1 SEE.13-415.AB.2 EXTERIOR LIGHTING. |
| | SHOW COMPLIANCE ON THE PLAN. THIS CAN BE DEMONSTRATED |
| | ON THE PLANS INDICATING THE WATTAGES OF THE LUMINAIRES |
| | CHOSEN FOR THE PROJECT CONFORM TO THE DENSITY |
| | REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE SCHEDULE |
| | TO CORRELATE WITH THE ONES IN THE CALCULATIONS. |
| | |
| | 2} THE 2008 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 1 OCTOBER 2009. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CHANGE ALL NOTES TO REFLECT THIS |
| | CHANGE. |
| | |
| | 3} THE GROUNDING ELECTRODE CONDUCTOR MUST BE A MINIMUM |
| | OF 1/0 PER 250.66 |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |